GEMÜ 1441 cPos-X
14 Parameter list
- Loosen the display holder by removing the two internal
screws (Tx 10) and swivel it upwards/forwards.
13.1.3 Basic operation of the app
Parameter settings
Search function for individual
parameters
Parameter
Main menu
Action functions
Selected favourites view
- Carry out initialization
- Find device (localization)
Operating mode
Setting operating modes
AUTO = automatic mode
MAN = manual mode
Test = test mode
OFF = inactive
NoINIT = not initialized
INIT = initialization active
Device status
Operating time display
Bar charts
Status display
The app has been developed in such a way that it can be oper-
ated intuitively. This overview only serves to explain the basic
navigation within the app. All other functions and setting op-
tions are described and explained directly in the app.
13.1.4 Emergency operation
If there is a fault in the product and/or the wireless interface,
the product has two internal buttons that can be used to per-
form the following actions. The buttons must first be exposed
by removing the cover.
Status
Left-hand button
Right-hand button
NoInit
operating
mode
(not initialized)
Manual control of
the valve actuator
→
Pneumatic con-
nection 2 is vented
Manual control of
the valve actuator
→
Pneumatic con-
nection 2 is aerated
AUTO, MAN, OFF,
TEST
operating
mode
Press and hold both buttons simultan-
eously for three seconds,
→
Delete the initialization and reset the
device to the default setting*
* The device is therefore simultaneously moved to the
NoInit
operating mode and, as a result, allows the connected pro-
cess valve to be controlled manually using the two buttons
14 Parameter list
Number
Parameter Description Settings
Initial set-
ting
-
Local
Bluetooth
name
Locally
used
Bluetooth
name
Serial num-
ber of the
device
M02
Device
functions
Device op-
erating
mode (po-
sitioner...)
M01
Operating
mode
Device op-
erating
mode
OFF, AUTO,
MANUAL,
TEST
AUTO