Supply voltage:
10 – 30 V DC
Output type:
passive
Temperature drift:
≤ ±0.5% of full flow
Resolution:
0.1 %
Short-circuit proof:
Yes
Overload proof:
Yes (up to 30 V DC)
6.7.3 Digital input
Function:
Can be selected using software
Input type:
passive
Input voltage:
Typically 24 V DC (7–30 V DC)
Logic level "1":
7–30 V DC
Logic level "0":
0–5 V DC
Input current:
Typically. 6 mA DC
6.7.4 Digital output
Note:
Limit the current consumption to < 15 mA.
Function:
selectable using software
Supply voltage:
Typically 24 V DC (7–30 V DC)
Output type:
passive
Logic level "1":
conductive
Logic level "0":
disabled
6.7.5 Travel sensor input (for travel length code S01 – remote potentiometer)
Note:
Travel sensor input is not galvanically isolated from the supply voltage/set value input.
Input voltage
range:
0 to U
P+
Supply
voltage UP+:
Typically 0.48 V DC
Resistance range of re-
mote potentiometers:
1.8–6 kΩ (ideal 5 kΩ ±20%)
6.7.6 Positioner data
Note:
Control diagram:
Default setting / The control characteristic is adjustable.
www.gemu-group.com
10 / 33
GEMÜ 1441 cPos-X
6 Technical data