11 Fail safe functions
Fail safe functions
Case
Error
Connection A1 (2)
Connection A2 (4)
1
Power supply failure
Single acting fail safe: Venting
Single acting fail freeze: Blocking
Double acting fail safe: Venting
Double acting fail freeze: Blocking
Single acting: - (No connection avail-
able)
Double acting fail safe: Venting
Double acting fail freeze: Blocking
2
Compressed air supply failure
Single acting fail safe: Venting
Single acting fail freeze: Blocking
Double acting fail safe: Venting
Double acting fail freeze: Blocking
Single acting: - (No connection avail-
able)
Double acting fail safe: Venting
Double acting fail freeze: Blocking
However, the fail safe function does not replace the plant-specific safety devices.
Adjustable safety reactions
Error
Connection A1 (2)
Connection A2 (4)
Set value < 4 mA
(range below the set value under I Min W
can be adjusted 0–22 mA)
Single and double acting
Adjustable function
(Open, Close, Hold, Safe*)
Single acting: (Connection not available)
Double acting: Adjustable function
(Open, Close, Hold, Safe*)
Set value > 20 mA
(range below the set value I max can be
adjusted from 0–22 mA)
Single and double acting
:Adjustable function
(Open, Close, Hold, Safe*)
Single acting: (Connection not available)
Double acting: Adjustable function
(Open, Close, Hold, Safe*)
* Safe = default setting. In this case, the valve actuator is moved to its safety position (undefined for double acting)
GEMÜ 1441 cPos-X
www.gemu-group.com
21 / 33
11 Fail safe functions