www.gemu-group.com
27 / 33
GEMÜ 1441 cPos-X
Number
Parameter Description Settings
Initial set-
ting
S03
Hardware
version
Hardware
version
S04
Software
version
Software
version
S11
Production
number
Traceability
number of
the device
-
Operating
hours since
last start
Operating
hours at
device
start
-
Total oper-
ating hours
Operating
hours
P29
Function
digital in-
put
Function of
the digital
input
OFF, OFF /
ON, Safe /
ON, Parm-
SetB0, Poti,
Start Init
OFF
S07
Status di-
gital input
Signal ap-
plied at the
digital in-
put
P30
Function
digital out-
put
Function of
the digital
output
no, P min,
P max, P
min/max,
W min, W
max, W
min/max, X
min, X max,
X min/max,
SSE min,
SSE max,
SSE min/
max, Act-
ive, Error,
Warning
no
P35
Logic di-
gital output
Defines the
logic of the
digital out-
put
NO, NC
NO
P40
Time delay
digital out-
put
Defines the
time delay
of the di-
gital output
0.1 to
100.0 s
1.0 s
P31
Digital out-
put min
Lower
switch
point of the
digital out-
put
0.2 to
99.8%
10.0%
P32
Digital out-
put max
Upper
switch
point of the
digital out-
put
0.2 to
99.8%
90.0%
Number
Parameter Description Settings
Initial set-
ting
S08
Status di-
gital output
Status of
digital out-
put
S12
Active
parameter
set
Displays
the active
parameter
set
P1, P2
P1
P25
Copying
parameter
set
Copy to dif-
ferent
memories
off, P1 <=
W, P1 =>
P2, P1 <=
P2
off
P28
Initializa-
tion start
via magnet
Initializa-
tion option
via magnet
contact
P41
Display ori-
entation
Display ori-
entation
0°, 180°
0°
P42
Full-screen
display
Full-screen
display
off, on
off
-
Location
function
Device loc-
ation func-
tion
off, on
off
The parameters without numbers cannot be located in the app via the
"Parameters" menu.
15 Messages and troubleshooting
Message
ID
and type
Description
Cause and remedial measures
1
Error
Not calib-
rated
Device not calibrated.
- Send to GEMÜ for repair.
2
Warning
Not initial-
ized
Device not initialized.
- Carry out initialization.
10
Error
Set value <
4 mA
The set value signal is lower than
4 mA.
- Check the set value signal (if the
minimum current signal is not
reached, the device switches
off).
11
Error
Set value >
20 mA
The set value signal is higher than
20 mA.
- Check the set value signal.
15 Messages and troubleshooting