- 17 -
PARAMETER LIST
C
543
PmaxHuKw
Maximum boiler output in kW (Hu)
0...32766
kW
9 kW
13 kW
25 kW
50 kW
Type 2-13
-
-
-
Type 2-17
-
17 kW
-
-
Type 10-35 SEP
-
-
-
35kW
O
551
Kon
Constant for quick setback without room
influence
0...20 4
4
4
4
C
552
HydrSystem
Hydraulic system adjustment :
Type C/S/M40/M75/B120
0...255
3
3
3
3
Type DC
-
60
60
-
Type 5-25 SEP
-
-
7
-
Type 10-35 SEP/
10-50 SEP
-
-
-
7
C
553
KonfigHks
Configuration of heating circuits (signification:
KonfigHks = YX: HC1 run by RUX, HC2 by
RUY . X,Y = [0,1,2], AA0: no room influence
0...255 21
21
21
21
C
555
KonfigRg1
Setting flags
0...255
10010000 10010000 10010000 10010000
C
561
KonfigRg7
Setting flags for a modulating pump
0...255
00001101 00001101 00001101 00001101
Type 5-25 SEP
-
-
00001101 -
Setting flags for a non-modulating pump
0...255
00001100 00001100 00001100 00001100
Type 5-25 SEP/
10-35 SEP
-
-
00001100
00001100
O
598
LmodRgVerz Output during controller delay time
(LmodTL
≤
LmodRgVerz
≤
LmodVL)
0...100 % 18%
18%
18%
16%
C
614
Konfig-
Eingang
Progr input LMU basis
0: Default, programmable input function is not
used
1: Modem function active when contact is closed,
2: Modem function active when contact is open
3: Warm air curtain function
1
1
1
1
1
C
615
Konfig-
Ausgang
Function programmable output K2 LMU
0: Default (function according to the hydraulic
diagram)
1: Status output,
2: Alarm output
3: Operational signal
4: Switching off external transformer
5: Pump of the second heating circuit
6: DHW circulating pump
7: Actuating device with warm air curtain
activated
8: Pump of the pressureless header
9: Basic function of controller clip-in module
10: Basic function K2,
11: Actuating device with full DHW charging
activated, in connection with stratification
storage tanks,
12: Actuating device when analog signal (at the
clip-in function module) has exceeded the
threshold
0...255 0
0
0
0
O
623
PAnfoExt-
Schwelle
Threshold of analog signal from which the
external demand for output will be accepted
(percentage of maximum value of analog
signal)
5...95 % 5 %
5 %
5 %
5 %
C
632
WAnfoQ8
Heat demand to be supported by the system
pump Q8
0...255
00000000 00000000 00000000 00000000
C
639
dTUeberhBegr Limitation of temperature boost by dT control 0...100 % 40 %
40 %
40 %
40 %
C
658
Estrich-
FunktionRh1
Mode of floor curing function for space heating
1 :
0: inactive
1: Active
0
0
0
0
0
C
659
Estrich-
FunktionRh2
Mode of floor curing function for space heating
2 :
0: inactive
1: Active
0
0
0
0
0
Level Line
Display
Function
Range
Factory setting : boiler version
0.9-9
2-13/2-17
5-25
10-50