background image

- 13 -

IV - PARAMETER LIST

1 - PARAMETER LIST QAA73 (STORED IN THE QAA73 FROM 1 TO 199)

1.1 - Overview of end-user parameters

* These lines are only displayed in OpenTherm Plus mode. Also, the relevant functions must be supported by boiler control.
 

- - : - - 

= Switching point inaktiv

Line

Function

Range/display

Unit

Resolution

Factory 

setting

Time of day

1

Time of day

0...23:59

hh:mn

1 min

-

2

Date (day, month)

1. jan ... 31 dec

tt:mm

1 day

-

3

Year

2000 ... 2094

yyyy

1 year

-

Set points

5

Reduced room temperature setpoint  (TRRw)

TRF ... TRN

°C

0.5

16.0

6

Frost protection setpoint of room temperature (TRF)

4 ... TRRw

°C

0.5

10.0

7*

Nominal setpoint of d.h.w. temperature (TBWw)

TBWR ... TBWmax

°C

1

60

Time switch program HC1 (heating circuit 1)

10

Preselection of weekday

Mo...Su, week

Weekday 1 day

-

11

switch-on time

1st phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

06:00

12

switch-off time 

1st phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

22:00

13

switch-on time

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

14

switch-off time 

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

15

switch-on time

3rd phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

16

switch-off time 

3rd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

Time switch program HC2 (heating circuit 2)

20*

Preselection of weekday

Mo...Su, week

Weekday 1 day

-

21*

switch-on time

1st phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

06:00

22*

switch-off time 

1st phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

22:00

23*

switch-on time

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

24*

switch-off time 

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

25*

switch-on time

3rd phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

26*

switch-off time 

3rd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

Time switch program domestic hot water

30

Preselection of weekday

Mo...Su, week

Wekday

1 day

-

31

switch-on time

1st phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

06:00

32

switch-off time 

1st phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

22:00

33

switch-on time

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

34

switch-off time 

2nd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

35

switch-on time

3rd phase 

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

36

switch-off time 

3rd phase

- - : - - / 00:00 ... 24:00 hh:mn

10 min

--:--

Holidays

40

Holidays start (day.month)   

 - - : - - = inactif

1. jan ... 31 dec

tt.mm

1 day

- - : - -

41

Holidays end (day.month)     

  - - : - - = inactif

1. jan ...  31 dec

tt.mm

1 day

- - : - -

42

Heating circuit operating level during holidays

Frost, reduced

-

-

Frost

General

45

STANDARD time switch programs for HC1 + 2 and 
d.h.w. 

(press both buttons -/+ for 3 s)

No, yes

-

-

no

46

Summer / winter changeover temperature

8 ... 30

°C

0.5

19.0

47

Language German, 

English

-

-

English

50*

Display of fault (error code of QAA73.110 or boiler 
control)

0 ... 255

-

1

-

Summary of Contents for QAA 73.110

Page 1: ...N O T I C E T E C H N I Q U E la chaleur haute fidélité QAA 73 110 Constructeur T30 32961 09 Constructeur ...

Page 2: ... GESTION LMU VIA LA QAA 73 8 4 1 NIVEAU 4 PARAMETRAGE PAR L UTILISATEUR FINAL 8 4 2 NIVEAU 5 PARAMETRAGE PAR LE CHAUFFAGISTE 9 4 3 NIVEAU 6 PARAMETRAGE OEM 10 III DEFAUTS DE FONCTIONNEMENT 12 IV LISTES DES PARAMETRES 13 1 LISTE DES PARAMETRES QAA 73 MEMORISES DANS LA QAA73 DE 1 A 199 13 1 1 Liste des paramètres UTILISATEUR FINAL 13 1 2 Liste des paramètres CHAUFFAGISTE 14 1 3 Liste des paramètres ...

Page 3: ...ture Humidité Transport Température Humidité Stockage Température Humidité CEI 721 3 3 classe 3K5 0 50 C 85 hum rel CEI 721 3 2 classe 2K3 25 70 C 95 hum rel CEI 721 3 1 classe 1K3 25 70 C 95 hum rel Normes Conformité CE Directive en matière de CEM Sensibilité aux influences parasites Rayonnements perturbateurs Directive relative à la basse tension Sécurité électrique 89 336 CEE EN 50082 1 EN 5008...

Page 4: ... by veille 6 Touches de régime Eau chaude sanitaire Marche Arrêt Eau Chaude Sanitaire 7 Touches de sélection de ligne Sélection de la ligne de commande 8 Touches de réglage Réglage des paramètres a THI 59 0 b c d e f g h Fig 2 a Température ambiante mesurée b Niveau de fonctionnement du circuit de chauffa ge confort Economie Hors gel c Etat de flamme actif si présence de flamme d Indication défaut...

Page 5: ...e ligne choisissez la ligne voulue rep b Les possibilités de réglage sont indiquées au 1 1 chapitre IV LISTES DES PARAMETRES 3 Régler la valeur désirée à l aide des touches ou rep c Le réglage est mémorisé dès que vous quittez le mode programmation ou passez à une autre ligne Les possibilités de réglage sont indiquées au 1 1 chapitre IV LISTES DES PARAMETRES 4 En appuyant sur la touche Info vous q...

Page 6: ...tion chauffagiste niveau 2 Affichage 3 A l aide des touches de sélection de ligne choisissez la ligne voulue rep b toutes les lignes possibles figurent au 1 2 chapitre IV LISTES DES PARA METRES 4 Régler la valeur désirée à l aide des touches ou rep c Le réglage est mémorisé dès que vous quittez le mode programmation ou passez à une autre ligne Les possibilités de réglage sont indiquées au 1 2 chap...

Page 7: ...uches de sélection ou et Prog Combinaison correcte vous entrez dans le mode de programmation OEM Affichage Combinaison erronée l affichage revient au paramètrage chauffagiste ligne 51 Affichage 4 A l aide des touches de sélection de ligne choisissez la ligne voulue rep b toutes les lignes possibles figurent au 1 3 chapitre IV LISTES DES PARA METRES 5 Régler la valeur désirée à l aide des touches o...

Page 8: ...he Remarque Ligne 1 et Appuyer simultanément sur la touche de sélection de ligne et la touche de réglage en commençant par la touche Vous accédez au premier niveau de programmation du LMU niveau 4 Affichages successifs 2 A l aide des touches de sélection de ligne choisissez la ligne voulue rep b toutes les lignes possibles figurent au 2 chapitre IV LISTES DES PARAME TRES 3 Régler la valeur désirée...

Page 9: ...élection de ligne pendant 3 s minimum Vous accédez au 2ème niveau de programmation du LMU niveau 5 Affichages successifs 3 A l aide des touches de sélection de ligne choisissez la ligne voulue rep b toutes les lignes possibles figurent au 2 chapitre IV LISTES DES PARAME TRES 4 Régler la valeur désirée à l aide des touches ou rep c Le réglage est mémorisé dès que vous quittez le mode programmation ...

Page 10: ...ouche Vous accédez au premier niveau de programmation du LMU niveau 4 Affichages successifs 2 Appuyer simultanément sur les deux touches de sélection de ligne pendant 3 s minimum Vous accédez au deuxième niveau de programmation du LMU niveau 5 Affichages successifs 3 Appuyer simultanément sur les deux touches de sélection de ligne pendant 9 s minimum Un affichage spécial apparaît entrée du code OE...

Page 11: ...tion de ligne choisissez la ligne voulue rep b toutes les lignes possibles figurent au 2 chapitre IV LISTES DES PARAME TRES 6 Régler la valeur désirée à l aide des touches ou rep c Le réglage est mémorisé dès que vous quittez le mode programmation ou passez à une autre ligne Les possibilités de réglage sont indiquées au 2 chapitre IV LISTES DES PA RAMETRES 7 En appuyant sur la touche Info vous qui...

Page 12: ...in de maintenance Si la cloche clignote ouvrir la façade de la QAA73 2 Appuyer sur la touche de sélection de ligne jusqu à la ligne 50 Le code défaut 62 apparaît la sonde d ambiance installée est incompatible avec la chaudière la remplacer Remarque si une autre alarme apparaît se référer à la liste des codes défauts THI 47 0 PROG THI 48 0 ...

Page 13: ... Circuit de chauffage 2 20 Présélection du jour de semaine Lu Di semaine jour 1 jour 21 Heure d enclenchement 1ère phase 00 00 24 00 hh mn 10 min 06 00 22 Heure d arrêt 1ère phase 00 00 24 00 hh mn 10 min 22 00 23 Heure d enclenchement 2ème phase 00 00 24 00 hh mn 10 min 24 Heure d arrêt 2ème phase 00 00 24 00 hh mn 10 min 25 Heure d enclenchement 3ème phase 00 00 24 00 hh mn 10 min 26 Heure d arr...

Page 14: ... 2 5 40 0 0 5 15 0 71 Limitation min de la temp de départ CC 1 TV1min 8 TV1max C 1 8 72 Limitation max de la temp de départ CC 1 TV1max TV1min TKmax C 1 80 73 Translation de la caractéristique de chauffe CC 1 4 5 4 5 K 0 5 0 0 74 Construction du bâtiment lourde légère légère 75 Influence de la température ambiante aucune sur CC 1 sur CC 2 sur CC1 CC 2 sur CC1 76 Différentiel d ambiance point de co...

Page 15: ...EM 100 Consigne max de temp ambiante TRwMax TRwMin 35 C 0 5 30 101 Consigne min de temp ambiante TRwMin 4 TRwMax C 0 5 10 102 Facteur d influence de la température ambiante KORR 0 20 1 4 103 Constante d abaissement accéléré KON sans sonde de température ambiante 0 20 1 4 104 Surélévation de la consigne de temp ambiante DTRSA Réchauffage rapide 0 20 K 1 5 105 Limitation de l augment de la consigne ...

Page 16: ...65 C 65 C 65 C 65 C Type 5 25 SEP 0 C Type 10 35 SEP 0 C Fonctions de régulateur Configuration C 532 Sth1 Pente de la caractéristique de chauffe circuit de chauffage 1 1 40 15 15 15 15 C 533 Sth2 Pente de la caractéristique de chauffe circuit de chauffage 2 1 40 8 8 8 8 C 534 DtR1 Correction consigne d ambiance circuit de chauffage 1 31 31 K 0 K 0 K 0 K 0 K C 535 DtR2 Correction consigne d ambianc...

Page 17: ... Activé 0 0 0 0 0 Temps du régulateur Tous les paramètres non relatifs à la sécurité O 603 Z_Bw Comfort2 Temps de la fonction confort du chauffe eau instantané après un soutirage présence de demande de chauffage 0 désactivé 255 4h15min 0 255 min 10 min 10 min 10 min 10 min Type 5 25 SEP 5 min Type 10 35 SEP 5 min O 637 Z_PumpeAusUv Durée de l arrêt de la pompe lors du changeover CH ECS de la vanne...

Page 18: ...p in mélangeur O 596 ZeitAufZu Temps de course du servomoteur du mélangeur temps ouverture temps fermeture 30 873 s 150 s 150 s 150 s 150 s O 597 XpHz2 Bande P du régulateur du circuit de chauffage2 1 100 K 24 K 24 K 24 K 24 K Fonctions Clip in Relais C 618 Konfig EingangR Entrée programmable sur Relais Clip In 0 par défaut la fonction entrée programmable n est pas utilisée 1 Fonction modem active...

Page 19: ...Konfig Ausgang3R Fkt sortie3 Relais Clip In 0 Défaut 1 Sortie de signalisation 2 Sortie d alarme 3 Information de fonctionnement 4 Coupure transformateur externe 5 Pompe 2ème circuit de chauffage 6 Pompe eau chaude sanitaire 7 Fonction rideau d air chaud 8 Fonction découpleur hydraulique 9 Fonction élémentaire clip in relais 10 Fonction élémentaire K2 11 Sortie active pendant la charge continue du...

Page 20: ...e valeur d historique du code de dérangement Albatros C 709 Stoer4 4ème valeur d historique du nombre d apparition de ce code de dérangement C 710 StrPn4 4ème valeur d historique de la phase de dérangement C 711 StrDia4 4ème valeur d historique du code de diagnostic interne C 731 StrAlba4 4ème valeur d historique du code de dérangement Albatros C 712 Stoer5 5ème valeur d historique du nombre d app...

Page 21: ...T E C H N I C A L I N S T R U High fidelity heat C T I O N S QAA 73 110 Manufacturer T30 32961 09 Manufacturer ...

Page 22: ... THE CONTROL UNIT LMU VIA THE QAA73 8 4 1 4 Level Parameter settings for the end user 8 4 2 5 Level Parameter settings for the heating engineer 9 4 3 6 Level Parameter settings for the OEM 10 III OPERATING FAULTS 12 IV PARAMETER LIST 13 1 PARAMETER LIST QAA73 STORED IN THE QAA73 FROM 1 TO 199 13 1 1 Overview of end user parameters 13 1 2 Overview of heating engineer parameters 14 1 3 Overview of O...

Page 23: ...to EN 60730 Environmental conditions Operation Temperatures Humidity Transport Temperatures Humidity Storage Temperatures Humidity IEC 721 3 3 class 3K 5 0 50 C 85 r h IEC 721 3 2 class 2K 3 25 70 C 95 r h IEC 721 3 1 class 1K 3 25 70 C 95 r h Standards CE conformity EMC directive Immunity Emissions Low voltage directive Electrical safety 89 336 EEC EN 50082 1 EN 50082 2 EN 50081 1 EN 50081 2 73 2...

Page 24: ...eration continuous operation Standby 6 D h w operating mode button with associated symbol D h w heating ON OFF 7 Line selection buttons Selection of operating line 8 Setting buttons Setting the parameters a THI 59 0 b c d e f g h Fig 2 a Actual value of room temperature b heating circuit operating level nominal reduced Frost proctection c Flame status activated if flame present d Fault service e T...

Page 25: ... required line rep b The parameter list containing all possible settings is indicated in 1 1 section IV Parameter list 3 Press the plus or minus button to enter the required value rep c The setting will be stored as soon as you leave the programming mode or change to another line The parameter list containing all possible settings is indicated in 1 1 section IV Parameter list 4 By pressing the Inf...

Page 26: ... Heating engineer 2 level Display 3 Press the line selection buttons to select the required line rep b All possible lines are indicated in 1 2 section IV Parameter list 4 Press the plus or minus button to enter the required value rep c The setting will be stored as soon as you leave the programming mode or change to another line The parameter list containing all possible settings is indicated in 1...

Page 27: ... Correct combination you reach the programming mode OEM Display Wrong combination the display will change to the Parameter settings for the heating engineer line 51 Display 4 Press the line selection buttons to select the required line rep b All possible lines are indicated in 1 3 section IV Parameter list 5 Press the plus or minus button to enter the required value rep c The setting will be store...

Page 28: ...the both line selection buttons and setting buttons beginning with the button This will take you to the first programming mode LMU 4 level Successive display 2 Press the line selection buttons to select the required line rep b All possible lines are indicated in 2 section IV Parameter list 3 Press the plus or minus button to enter the required value rep c The setting will be stored as soon as you ...

Page 29: ...least 3 seconds This will take you to the second programming mode LMU 5 level Successive display 3 Press the line selection buttons to select the required line rep b All possible lines are indicated in 2 section IV Parameter list 4 Press the plus or minus button to enter the required value rep c The setting will be stored as soon as you leave the programming mode or change to another line The para...

Page 30: ...ns beginning with the button This will take you to the first programming mode LMU 4 level Successive display 2 Press both line selection buttons for at least 3 seconds This will take you to the second programming mode LMU 5 level Successive display 3 Press both line selection buttons for at least 9 seconds A special display will appear entering the OEM code for the manufacturer Display PROG THI 54...

Page 31: ...tons to select the required line rep b All possible lines are indicated in 2 section IV Parameter list 6 Press the plus or minus button to enter the required value rep c The setting will be stored as soon as you leave the programming mode or change to another line The parameter list containing all possible settings is indicated in 2 section IV Parameter list 7 By pressing the Info button you leave...

Page 32: ...lt or when maintenance is required If the bell is flashing open the QAA73 front cover 2 Press the line selection button up to the line 50 Fault code 62 is displayed the room sensor is incompatible with the boiler re place it Note If another alarm is displayed refer to the list of fault codes THI 47 0 PROG THI 48 3 ...

Page 33: ...HC2 heating circuit 2 20 Preselection of weekday Mo Su week Weekday 1 day 21 switch on time 1st phase 00 00 24 00 hh mn 10 min 06 00 22 switch off time 1st phase 00 00 24 00 hh mn 10 min 22 00 23 switch on time 2nd phase 00 00 24 00 hh mn 10 min 24 switch off time 2nd phase 00 00 24 00 hh mn 10 min 25 switch on time 3rd phase 00 00 24 00 hh mn 10 min 26 switch off time 3rd phase 00 00 24 00 hh mn ...

Page 34: ...slope HC1 HC 1 inactive 2 5 40 0 0 5 15 0 71 Minimum limitation of flow temperature HC 1 TV1min 8 TV1max C 1 8 72 Maximum limitation of flow temperature HC 1 TV1max TV1min TKmax C 1 80 73 Parallel displacement of heating curve HC 1 4 5 4 5 K 0 5 0 0 74 Type of building construction Heavy light light 75 Room influence None on HC 1 on HC 2 on HC1 HC 2 on HC1 76 Switching differential of room tempera...

Page 35: ... temperature setpoint TRwMax TRwMin 35 C 0 5 30 101 Minimum room temperature setpoint TRwMin 4 TRwMax C 0 5 10 102 Gain factor of room influence KORR 0 20 1 4 103 Quick setback constant KON without room sensor 0 20 1 4 104 Boost of room temperature setpoint DTRSA boost heating 0 20 K 1 5 105 Limitation of rate of increase of flow temperature setpoint 0 15 K min 0 5 8 106 Measured value correction ...

Page 36: ...ction of room setpoint when using time switch dTrAbsenk 0 acting on heat demand 0 10 K 6 K 6 K 6 K 6 K C 521 dTkTrNenn Delta flow return temperature at TiAussenNorm 2 5K dTkTrMax 2 5 20 K 20 K 20 K 20 K 20 K O 622 TAnfoExtMax Maximum value of heat demand with external predefined temperature setpoint 5 C TAnfoExtMax 130 C 5 130 C 80 C 80 C 80 C 80 C C 657 TbwSollAleg Setpoint of autonomous legionel...

Page 37: ...r curtain function 1 1 1 1 1 C 615 Konfig Ausgang Function programmable output K2 LMU 0 Default function according to the hydraulic diagram 1 Status output 2 Alarm output 3 Operational signal 4 Switching off external transformer 5 Pump of the second heating circuit 6 DHW circulating pump 7 Actuating device with warm air curtain activated 8 Pump of the pressureless header 9 Basic function of contro...

Page 38: ...Modulation air when burner control is not operating 0 100 0 0 0 0 Maintenance alarms C 625 BetrStdWart Grenz Set limit for the number of operating hours interval since last service visit 0 9998 hrs 0 0 0 0 C 626 InbetrSetzWart Grenz Set limit for the number of startups interval since last service visit 0 9995 0 0 0 0 C 627 MonatWart Grenz Set limit for the number of months interval since last serv...

Page 39: ...the pressureless header 9 Basic function of controller clip in module 10 Basic function K2 11 Actuating device with full DHW charging activated in connection with stratification storage tanks 12 Actuating device when analog signal at the clip in function module has exceeded the threshold 0 255 10 10 10 10 C 620 Konfig Ausgang2R Function output2 clip in function module 0 Default function according ...

Page 40: ...ast value of ALBATROS error code C 703 Stoer2 2nd past value of lockout code counter C 704 StrPn2 2nd past value of lockout phase C 705 StrDia2 2nd past value of internal diagnostic code C 729 StrAlba2 2nd past value of ALBATROS error code C 706 Stoer3 3rd past value of lockout code counter C 707 StrPn3 3rd past value of lockout phase C 708 StrDia3 3rd past value of internal diagnostic code C 730 ...

Page 41: ...T E C H N I S C H E B E S C H R E I B U N G Wärmeerzeugung par excellence QAA 73 110 Hersteller T30 32961 09 Hersteller ...

Page 42: ... MITTELS LA QAA73 8 4 1 4 Bedienebene Parametrierung Endbenutzer 8 4 2 5 Bedienebene Parametrierung Heizungsfachmann 9 4 3 6 Bedienebene Parametrierung OEM 10 III BETRIEBSSTÖRUNGEN 12 IV PARAMETERLISTEN 13 1 PARAMETERLISTE QAA73 GESPEICHERT IM QAA73 1 BIS 199 13 1 1 Übersicht der Endbenutzer Parameter 13 1 2 Übersicht der Heizungsfachmann Parameter 14 1 3 Übersicht der OEM Parameter 15 2 PARAMETER...

Page 43: ...en Betrieb Temperaturen Feuchte Transport Temperaturen Feuchte Lagerung Temperaturen Feuchte CEI 721 3 3 Klasse 3K5 0 50 C 85 rH CEI 721 3 2 Klasse 2K3 25 70 C 95 rH CEI 721 3 1 Klasse 1K3 25 70 C 95 rH Normen und Standards CE Konformität EMV Richtlinie Störfestigkeit Emissionen Niederspannungsrichtlinie Elektrische Sicherheit 89 336 CEE EN 50082 1 EN 50082 2 EN 50081 1 EN 50081 2 73 23 CEE EN 607...

Page 44: ...b Dauerbetrieb Standby 6 Brauchwasserbetriebsart Taste Brauchwasser Ein Aus 7 Zeilenwahl Tasten Wahl der Bedienzeile 8 Einstell Tasten Verstellen der Einstellparameter a THI 59 0 b c d e f g h Fig 2 a Istwert der Raumtemperatur b Heizkreis Betriebsniveau Anzeige Nenn Reduziert Frostschutz c Flammenzustand aktiviert falls Flamme ein d Fehler Wartungshinweis e Zeitbalken f Uhrzeit g Betriebsarten He...

Page 45: ...de Zeile an rep b Die Einstellungsmöglichkeiten sind in Abschnitt 1 1 chapitre IV PARAME TERLISTEN dargestellt 3 Stellen Sie den gewünschten Wert mit der Plus oder Minustaste ein rep c Die Einstellung wird gespeichert sobald Sie die Programmierebene verlassen oder in eine andere Zeile wechseln Die Einstellungsmöglichkeiten sind in Abschnitt 1 1 chapitre IV PARAME TERLISTEN dargestellt 4 Durch Drüc...

Page 46: ...gsfachmann 2 Be dienebene Anzeige 3 Wählen Sie mit den Zeilenwahl Tasten die entsprechende Zeile an rep b Die möglichen Zeilen sind in Abschnitt 1 2 chapitre IV PARAMETERLISTEN dargestellt 4 Stellen Sie den gewünschten Wert mit der Plus oder Minustaste ein rep c Die Einstellung wird gespeichert sobald Sie die Programmierebene verlassen oder in eine andere Zeile wechseln Die Einstellungsmöglichkeit...

Page 47: ...stenkombination gelangen Sie in den Program mierbetrieb OEM Anzeige Wurde der Code falsch eingegeben wechselt die Anzeige wieder in die Parametrie rung Heizungsfachmann Zeile 51 Anzeige 4 Wählen Sie mit den Zeilenwahl Tasten die entsprechende Zeile an rep b Die möglichen Zeilen sind in Abschnitt 1 3 chapitre IV PARAMETERLISTEN dargestellt 5 Stellen Sie den gewünschten Wert mit der Plus oder Minust...

Page 48: ... Zeilenwahl Taste und die Einstell Taste wobei Sie mit der Taste beginnen Dadurch gelangen Sie auf die erste Programmier ebene LMU 4 Bedienebene Aufeinander folgende Anzeigen 2 Wählen Sie mit den Zeilenwahl Tasten die entsprechende Zeile an rep b Die möglichen Zeilen sind in Abschnitt 2 chapitre IV PARAMETERLISTEN dargestellt 3 Stellen Sie den gewünschten Wert mit der Plus oder Minustaste ein rep ...

Page 49: ...en Dadurch gelangen Sie auf die zweite Programmier ebene LMU 5 Bediene bene Aufeinander folgende Anzeigen 3 Wählen Sie mit den Zeilenwahl Tasten die entsprechende Zeile an rep b Die möglichen Zeilen sind in Abschnitt 2 chapitre IV PARAMETERLISTEN dargestellt 4 Stellen Sie den gewünschten Wert mit der Plus oder Minustaste ein rep c Die Einstellung wird gespeichert sobald Sie die Programmierebene ve...

Page 50: ...durch gelangen Sie auf die erste Programmier ebene LMU 4 Bedienebene Aufeinander folgende Anzeigen 2 Drücken Sie dann beide Zeilenwahl Tasten während mindestens 3 Sekunden Dadurch gelangen Sie auf die zweite Programmier ebene LMU 5 Bediene bene Aufeinander folgende Anzeigen 3 Drücken Sie dann beide Zeilenwahl Tasten während mindestens 9 Sekunden Es erscheint eine Spezial Anzeige OEM Code Eingabe f...

Page 51: ... Wählen Sie mit den Zeilenwahl Tasten die entsprechende Zeile an rep b Die möglichen Zeilen sind in Abschnitt 2 chapitre IV PARAMETERLISTEN dargestellt 6 Stellen Sie den gewünschten Wert mit der Plus oder Minustaste ein rep c Die Einstellung wird gespeichert sobald Sie die Programmierebene verlassen oder in eine andere Zeile wechseln Die Einstellungsmöglichkeiten sind in Abschnitt 2 chapitre IV PA...

Page 52: ...nkt das Glockensymbol In diesem Fall die Front des QAA73 öffnen 2 Drücken Sie die Zeilen Taste bis zur Zeile 50 Bei Anzeige des Störungscodes 62 Installierter Raumfühler nicht mit dem Kes sel kompatibel Fühler ersetzen Hinweis Bei Anzeige anderer Alarme die Liste der Störungscodes zu Rate zie hen THI 47 0 PROG THI 48 1 ...

Page 53: ...mm HK 2 Wochentag Vorwahl Mo So Woche Tag 1 Tag 21 Zeitschaltprogramm HK 2 Einschaltzeit 1 Phase 00 00 24 00 hh mn 10 min 06 00 22 Zeitschaltprogramm HK 2 Ausschaltzeit 1 Phase 00 00 24 00 hh mn 10 min 22 00 23 Zeitschaltprogramm HK 2 Einschaltzeit 2 Phase 00 00 24 00 hh mn 10 min 24 Zeitschaltprogramm HK 2 Ausschaltzeit 2 Phase 00 00 24 00 hh mn 10 min 25 Zeitschaltprogramm HK 2 Einschaltzeit 3 P...

Page 54: ...it HK 1 HK 1 inaktiv 2 5 40 0 0 5 15 0 71 Vorlauftemperatur Minimalbegrenzung HK1 TV1min 8 TV1max C 1 8 72 Vorlauftemperatur Maximalbegrenzung HK1 TV1max TV1min TKmax C 1 80 73 Parallelverschiebung Heizkennlinie HK1 4 5 4 5 K 0 5 0 0 74 Gebäudebauweise Schwer Leicht Leicht 75 Raumtemperatur Einfluss Raumführung Kein Auf HK1 Auf HK2 Auf HK1 HK2 Auf HK1 76 Raum Schaltdifferenz Ausschaltpunkt inaktiv...

Page 55: ...heizung OEM 100 Raumtemperatur Sollwertmaximum TRwMax TRwMin 35 C 0 5 30 101 Raumtemperatur Sollwertminimum TRwMin 4 TRwMax C 0 5 10 102 Raumtemperatur Einfluss Verstärkungsfaktor KORR 0 20 1 4 103 Schnellabsenkungskonstante KON ohne Raumtemperatur Fühler 0 20 1 4 104 Raumtemperatur Sollwertüberhöhung DTRSA Schnellaufheizung 0 20 K 1 5 105 Anstiegsbegrenzung Vorlauf Sollwert 0 15 K min 0 5 8 106 R...

Page 56: ...nkhöhe des Raumsollwertes bei Schaltuhranschluss dTrAbsenk 0 auf Heizanf wirkend 0 10 K 6 K 6 K 6 K 6 K C 521 dTkTrNenn Delta Vor Rück Temp bei TiAussenNorm 2 5K dTkTrMax 2 5 20 K 20 K 20 K 20 K 20 K O 622 TAnfoExtMax Wärmeanforderungs Maximalwert bei externer Temperatursollwertvorgabe 5 C TAnfoExtMax 130 C 5 130 C 80 C 80 C 80 C 80 C C 657 TbwSollAleg Sollwert der freilaufenden Antilegionellenfun...

Page 57: ...mfunktion aktiv wenn Kontakt geschlossen 2 Modemfunktion aktiv wenn Kontakt offen 3 Torschleierfunktion 1 1 1 1 1 C 615 Konfig Ausgang Fkt Programmierbarer Ausgang K2 LMU 0 Default 1 Meldeausgang 2 Alarmausgang 3 Betriebsmeldung 4 Abschaltung ext Trafo 5 Pumpe 2 Heizkreis 6 Bw Zirkulationspumpe 7 Stellorgan bei aktiver Torschleierfunktion 8 Pumpe hydraulische Weiche 9 Grundfunktion Regler Clip In ...

Page 58: ...trStdWart Grenz Eingestellte Grenze für Betriebsstunden Intervall seit letzter Wartung 0 9998 Std 0 0 0 0 C 626 InbetrSetzWart Grenz Eingestellte Grenze für Inbetriebsetzungen Intervall seit letzter Wartung 0 9995 0 0 0 0 C 627 MonatWart Grenz Eingestellte Grenze für Monate Intervall seit letzter Wartung 0 255 Monat 0 0 0 0 C 628 GeblaeseWart Grenz Eingestellte Grenze des Gebläsedrehzahl für Wartu...

Page 59: ...g Ausgang2R Fkt Ausg2 Clip In Funktionsmodul 0 Default 1 Meldeausgang 2 Alarmausgang 3 Betriebsmeldung 4 Abschaltung ext Trafo 5 Pumpe 2 Heizkreis 6 Bw Zirkulationspumpe 7 Stellorgan bei aktiver Torschleierfunktion 8 Pumpe hydraulische Weiche 9 Grundfunktion Regler Clip In 10 Grundfunktion K2 11 Stellorgan bei aktiver Bw Durchladung in Verbindung mit Schichtenspeicher 12 Stellorgan bei Analog Sign...

Page 60: ...3 3 Vergangenheitswert Störcode Albatros C 709 Stoer4 4 Vergangenheitswert des Störcode Zählers C 710 StrPn4 4 Vergangenheitswert der Stör Phase C 711 StrDia4 4 Vergangenheitswert Interner Diagnosecode C 731 StrAlba4 4 Vergangenheitswert Störcode Albatros C 712 Stoer5 5 Vergangenheitswert des Störcode Zählers C 713 StrPn5 5 Vergangenheitswert der Stör Phase C 714 StrDia5 5 Vergangenheitswert Inter...

Page 61: ... 21 NOTIZEN ...

Page 62: ... 22 NOTIZEN ...

Page 63: ... 23 NOTIZEN ...

Page 64: ...RANCE Tél 02 98 79 40 22 Télécopie 02 98 79 47 57 Internet http www geminox fr Ayant le souci d améliorer constamment ses produits GEMINOX se réserve le droit de modifier sans préavis les caractéristiques de ses appareils Document non contractuel FÉVRIER 2007 ...

Reviews: