DT109AX / DT107AX / DT106AX / DT105AX / DT104AX / DT102AX
AUTO-TUNE PID TEMPERATURE CONTROLLER
Attention, Risk of,
High Voltage,
Double / Reinforced NOT CE Mark
Danger, Warning Risk of Electric Shock
Insulation
Litter
TECHNICAL SPECIFICATION
•
Dimensions
: 109:96x96,107:72x72,105/106:48x96,104:48x48,102:35x77mm
•
Panel Cut-out
: 109:91x91,107:68x68,105/106:94x46,DT104:46x46,102:29x71mm
•
Display
: 4 Digits 7 Segment (PV), 4 digits 7 Segment (SV)
•
Sensor Type
: J,K,T,S,R type T/C, Pt100 selectable
•
Measuring Scale
: -100..600
o
C, J type T/C (Inpt=J), -100.0 .. 600.0
o
C, J type T/C (Inpt=J.0)
-100..1300
o
C, K type T/C (Inpt=k), -100.0..999.9
o
C, K type T/C, (Inpt=k.0)
-100..400
o
C, T type T/C (Inpt=t), -100.0 .. 400.0
o
C, T type T/C (Inpt=t.0)
0..1750
o
C, S type T/C (Inpt=S) 0 .. 1750
o
C, R type T/C (Inpt=r)
-100..600
o
C, Pt100, (Inpt=Pt) -100.0 .. 600.0
o
C, Pt100, (Inpt=Pt.0)
•
Resolution
: ± 1
o
C or ± 0.1
o
C
•
Accuracy
: ± 1 % (Over full scale)
•
Control Form
: ON-OFF or P, PI, PD, PID - selectable
•
Out Output
: Relay, 250VAC, 2A, Resistive load, (optional SSR)
•
Alarm Output
: Relay, 250VAC, 2A, Resistive load
•
Heat SET
: Lower Limit .. Upper Limit
o
C (H.Set)
•
Alarm SET
: AL.tY = Abs,-Abs; Lo.L .. UP.L
o
C (A.Set)
AL.tY = rel, -rel, bnd, -bnd, bn.i, -bn.i; -100 .. +100 / -100.0 .. +100.0
o
C
•
Heat Hysteresis
: 0 .. 50 / 0.0 .. 50.0
o
C (H.Hys); PID is active if set to 0
•
Alarm Hysteresis
: 1 .. 50 / 0.1 .. 50.0
o
C (A.Hys)
•
Proportional Band
: 5 .. 150
o
C (Pb.C)
•
Integral Time
: 0:00 .. 30:00 min:sec. (OFF if set to 0:00)
•
Derivative Time
: 0:00 .. 10:00 min:sec. (OFF if set to 0:00)
•
Control Period
: 1 .. 200 sec. (Ct)
•
Offset
: -100..+100
o
C / -100.0 .. +100.0
o
C (oFFS)
•
Heating/Cooling
: Selectable (only ON-OFF control form is active for cooling)
•
Cold. Junc. Comp.
: 0 .. 50
o
C (T/C)
•
Line Comp.
: 10 Ohm max. (3 wire Pt100)
•
Sensor Failure
: OUT output is active according to P.Err and Ct parameters in case of
sensor failure, measurement out of range or hardware fails to measure
input signal (OUT output is OFF if Perr is 0). For Alarm look “Alarm Output”.
•
Supply Voltage
: 100..240VAC, 50-60Hz or (24VDC/AC; isolation voltage: 40VAC max.)
•
Power Consumption
: < 8VA
•
Humidity
: < 70% (non-condensing)
•
Altitude
: < 2000 m
•
EMC
: EN 61000-6-1, EN 61000-6-3 (Only light industrial environment)
•
Safety
: EN 61010-1; Pollution degree 1, measurement category
I
, (Only light industrial
environment, double/reinforced isolated, non-conductive pollution environment)
•
Protection Class
: IP20; according to EN 60529
•
Temperature Spec.
: Operating: 0 .. 50
o
C, Storage -10
o
C .. 60
o
C (no icing)
•
Weight
: < 0.5 kg
•
Torque for screwing
: Max. 0.5 N.m
WARNING:
if 2 wire Pt100 is used, connect compensation lead
to measuring lead: (DT109 / DT105 / DT106:
17-18
, DT107:
13-14
,
DT104:
10-11
, DT102:
9-10
)
no:
normally open
nc:
normally closed