Unless otherwise specified at time of purchase, units are calibrated in a vertical position, with lead wires up.
Install unit in piping system, using standard pipe fitting procedures.  Hold inlet fitting with wrench at installation
to prevent  fitting torque accumulation. Be sure to keep thread sealing compound out of unit.  Make sure that
flow is in proper direction - marked 

"IN" 

and 

"OUT"

 on housing.  See  wiring diagrams for electrical connections.

  

CAUTION:

  See "Switch Ratings" before connecting power.

CAUTION: 

 Flow settings for

 FS-920

 series switches are normally calibrated using water** @ +70°F on

increasing flow.  If unit will be used to monitor liquids other than water, gas or air, Factory should have been
consulted at time of purchase for special calibration.  All air/gas units are factory-calibrated using a special
piston.  Water-calibrated units are not recommended for air/gas applications.

**

Note

:  Flow settings for

 FS-930 

Viscosity Compensating type switches are calibrated in a vertical position

    (lead wires up) with 300 SSU oil.  Set points will be maintained within 20% of settings in a liquid viscosity
    range of 40 to 2,000 SSU.

Installation . . .

Piston-Type Flow Switches

Series FS-925/926 & FS-927/930

Instruction Bulletin No. 72949

Wetted Materials
  Housing
  Piston
    Brass Housing
    Stainless Steel Housing
  Spring
  O-Ring
  Other Wetted Parts
Pressure Rating
  Operating
  Proof
  Burst
Operating Temperature
  Brass or SS Piston
  Polysulfone Piston
Repeatability
Set Point Accuracy
Set Point Differential
Switch*
Inlet/Outlet Ports
Electrical Termination

Brass
Brass

Brass
Brass

Brass or 316 SS

Polysulfone/Water - Brass/Oil or Air

316 SS

Viton

®

N/A

Epoxy

1000 PSIG
2500 PSIG
5000 PSIG

SS

1000 PSIG,Max.

-20°F to +300°F
-20°F to +225°F

-20°F to +200°F

-20°F to +300°F

15%, Max.

1% Maximum Deviation

±10%

15% Max.(FS-925) - 20% (FS-926)

SPDT, 20 VA

1/4" NPT

No. 18 AWG, 24" L., Polymeric Lead Wires

FS-925/FS-926

FS-930

FS-927

316 SS

N/A
N/A

N/A
N/A

±15%

20% Max.

SPST, 20 VA

1/4" NPT

No. 18 AWG, 24" L.,

PVC Lead Wires

Specifications . . .

P/N 72949

Rev. P

Important Points!

Product must be maintained and installed in strict ac-
cordance with the National Electrical Code and Gems
product catalog  and instruction bulletin.  Failure to ob-
serve this warning could result in serious injuries or
damages.

An appropriate explosion-proof enclosure or intrinsically
safe interface device must be used for hazardous area
applications involving such things as 

(but not limited to)

ignitable mixtures, combustible dust and flammable mate-
rials.

*** Warning: To prevent ignition of flammable or combus-
tible atmospheres, disconnect power before servicing.

Pressure and temperature limitations shown on individual
catalog pages and drawings for the specified flow switches
must not be exceeded.  These pressures and tempera-
tures take into consideration possible system surge pres-
sures/temperatures and their frequencies.

Selection of materials for compatibility with the media is
critical to the life and operation of GEMS flow switches.
Take care in the proper selection of materials of construc-
tion; particularly wetted materials.

Life expectancy of switch contacts varies with appli-
cations.  Contact GEMS if life cycle testing is required.

Ambient temperature changes do affect switch set
points, since the specific gravity of a liquid can vary with
temperature.

Flow switches have been designed to resist shock and
vibration; however, shock and vibration should be mini-
mized.

Liquid media containing particulate and/or debris
should be filtered to ensure proper operation of GEMS
products.

Electrical entries and mounting points may require liq-
uid/vapor sealing if located in an enclosed tank.

Flow switches must not be field repaired.

Physical damage sustained by the product may ren-
der it unserviceable.