ACTRONIC
®
Profibus DP
Operating instructions
SideStep
®
Industrial
OPEN/CLOSE
17/42
7.4.15. GoOpen
The motor moves the valve to the open position. Once the valve is in the required
position, this needs to be communicated to the SideStep. This then takes the position as
"open".
.
Instruction from the master:
0xYY
0x41 (“A“)
0x00, 0x06 Function
1 byte
1 byte
2 bytes
4 bytes
Function:
Go to open position
0x00,0x00,0x00,0x01
In open position
0x00,0x00,0x00,0x02
Cancel Open function (ESC) 0x00,0x00,0x00,0x03
Response of the SideStep:
0xYY
0x41 (“A“)
0x00, 0x06 Status
1 byte
1 byte
2 bytes
4 bytes
Status:
Go to open position
0x00,0x00,0x00,0x01
In open position
0x00,0x00,0x00,0x02
Open function cancelled
0x00,0x00,0x00,0x03