1. Product Description.

  

 

 

The  electro-pneumatic  positioner  is  used  for  linear  valve  operations  with  pneumatic 
actuators via an electric controller or control system using an analogue output signal of 4 
– 20 mA. 
This  can  be  used  on  double  or  single  effect  actuators.  Easy  adjustment  from  zero  to 
span. Easy to change rotation (clockwise / anti-clockwise). 
Low consumption of air and easy connection of air tubes. 

 

 
2. Technical Data and Specifications 
 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Positioner Technical Specifications

 

Input signal 

4 ~ 20 mA DC 

Impedance 

250 ± 15Ω 

Input pressure 

1.4 ~ 7 kgf/cm

2

 (20  ~ 100psi)

 

Stroke 

Lineal  10 

– 150 mm 

Air connection 

G  (

NPT)1/4” 

Gauge connection 

G (NPT)1/8” 

Duct 

M20 x 1.5 

ATEX protection 

Non-Explosion 

Protection 

IP66 

Ambient temperature 

-20°C ~ 70°C 

Linearity 

± 1.5 % F.S. (full scale) 

Hysteresis 

± 1.5 % F.S. (full scale) 

Sensitivity 

± 0.4 % F.S. (full scale) 

Repeatability 

± 0.5% 

Air consumption 

3 LPM (Sup =1.4kgf/cm

2

, 20psi)

 

Flow capacity 

80 LPM (Sup =1.4kgf/cm

2

, 20psi) 

Material 

Aluminium alloy 

Weight 

2.8 kg (6.2 Ib) 

Summary of Contents for 5952 00

Page 1: ...8 L Hospitalet de Llobregat Barcelona Spain genebre genebre es www genebre es GENEBRE S A LAST UPDATE 17 06 2019 UPDATE NUMBER 1 1 INSTALLATION OPERATION AND MAINTENANCE MANUAL Positioner for Pneumati...

Page 2: ...onditions 5 5 Preliminary Checks 5 6 Positioner Installation 5 6 1 Installation of support and positioner over the valve 5 6 2 Connection to the transmission lever 6 6 3 Modification of the Adjustment...

Page 3: ...pan Easy to change rotation clockwise anti clockwise Low consumption of air and easy connection of air tubes 2 Technical Data and Specifications Positioner Technical Specifications Input signal 4 20 m...

Page 4: ...ings and notes detailed in these instructions Failure to observe the warnings and notes could result in personal injury and material damage Certain parts of the positioner are subject to mechanical mo...

Page 5: ...acing directly on the floor Use pallets shelving or wooden bases Genebre S A recommends a visual inspection to check for any possible damage during transport and storage The visual inspection must inc...

Page 6: ...ATE NUMBER 1 6 6 2 Connection to the transmission lever The position of the valve stem and the lever must form a right angle when the input signal is at 50 6 3 Modification of the Adjustment Device SP...

Page 7: ...the Regulation lever Rotate the Span Regulation device 180 until the span adjustment screw is in the position opposite the gauge see diagram Secure the Regulation Lever in place with the screw If it...

Page 8: ...as follows 1 Use a regulator with a filter to maintain a constant air supply pressure optimum supply pressure of 6 bar to operate the actuator 2 Completely purge the circuit of air to avoid any forei...

Page 9: ...E S A LAST UPDATE 17 06 2019 UPDATE NUMBER 1 9 Art 5952 00 Art 5952 04 Detail of connection to the transmitter Art 5951 04 Once the connections are completed replace the cover and close using the scre...

Page 10: ...actory 8 1 Zero Setting This sends the stroke start signal 4 mA Rotate the ZERO adjustment wheel clockwise or anti clockwise until the reference lines of the indicator cam match the closed position of...

Page 11: ...d repeat the Span adjustment as many times as necessary Once the equipment has been adjusted tighten the locking screw 8 3 Auto Manual Switch This control is used to switch between Auto and Manual mod...

Page 12: ...Air throttle in pilot valve In the case of actuators with low air capacity this could cause oscillation on the equipment rendering it inoperable In this case use air throttles in outlets OUT1 and OUT2...

Page 13: ...button and the indicator light flashes indicating that regulation begins Observe the aperemeter value the value should be 4 mA if there is deviation can press the button or button adjust the current...

Page 14: ...16 mA to 20 mA around means the feedback signal 75 16 mA position confirmed Module waiting for the feedback signal 100 20 mA position confirm 8 6 7 Feedback signal 100 20 mA position adjusting The va...

Page 15: ...as set out below Disconnect any air or electricity supply Remove the A M Switching regulator from the pilot valve Insert the wire attached to the interior of the cover through the air inlet located i...

Reviews: