background image

 

 

 
Edificio Genebre. Av. de Joan Carles I, 46-48 
08908 L'Hospitalet de Llobregat. Barcelona (Spain) 
genebre@genebre.es   - www.genebre.es 

 

 

GENEBRE S.A. 

LAST UPDATE: 17/06/2019         UPDATE NUMBER:  1 

 
 

4. Transport and Storage Conditions 

 

  The positioners are dispatched from the Genebre, S.A. facilities in suitable 

packaging to prevent any blows. 

  Any sling, rope or chain used to lift or transport the motorised valves must 

NOT

 

be attached to the positioner under any circumstances. 

  The supports of the positioner are designed to bear operating stresses, 

NOT

 

the total weight of the valve, nor any other type of load or stress. 

  Do 

NOT

 knock the positioner against walls, floors or other devices. This may 

cause severe damage to the positioner or its components. 

  Store in a dry and well ventilated place, protected from weather conditions. 

Avoid placing directly on the floor. Use pallets. shelving or wooden bases. 

  Genebre, S.A. recommends a visual inspection to check for any possible 

damage during transport and storage. The visual inspection must include the 
interior of the compartments.

 

 
 

5. Preliminary Checks 

 

  Verify that the characteristics of the positioner correspond to the characteristics 

required prior to installation and start-up These data can be found on the 
nameplate.

 

  In the case of a deviation or non-conformity, contact Genebre, S.A.

 

 

 

 
 

 

 

Maximum air supply pressure 7 kgf/cm² (100 psi) 

 

 
6. Positioner Installation

 

 
6.1 Installation of Support and Positioner over the valve 
 

 

The installation of the positioner over the valve will depend on its design.

 

The positioner comes with a series of accessories within its packaging to cover 
practically all different types of assembly.

 

 
Installation examples over a Regulator and Control Valve: 
 

Ensure that the air supply to be used is dry, clean and filtered as a 
poor quality air supply could severely damage the positioner.

 

Summary of Contents for 5952 00

Page 1: ...8 L Hospitalet de Llobregat Barcelona Spain genebre genebre es www genebre es GENEBRE S A LAST UPDATE 17 06 2019 UPDATE NUMBER 1 1 INSTALLATION OPERATION AND MAINTENANCE MANUAL Positioner for Pneumati...

Page 2: ...onditions 5 5 Preliminary Checks 5 6 Positioner Installation 5 6 1 Installation of support and positioner over the valve 5 6 2 Connection to the transmission lever 6 6 3 Modification of the Adjustment...

Page 3: ...pan Easy to change rotation clockwise anti clockwise Low consumption of air and easy connection of air tubes 2 Technical Data and Specifications Positioner Technical Specifications Input signal 4 20 m...

Page 4: ...ings and notes detailed in these instructions Failure to observe the warnings and notes could result in personal injury and material damage Certain parts of the positioner are subject to mechanical mo...

Page 5: ...acing directly on the floor Use pallets shelving or wooden bases Genebre S A recommends a visual inspection to check for any possible damage during transport and storage The visual inspection must inc...

Page 6: ...ATE NUMBER 1 6 6 2 Connection to the transmission lever The position of the valve stem and the lever must form a right angle when the input signal is at 50 6 3 Modification of the Adjustment Device SP...

Page 7: ...the Regulation lever Rotate the Span Regulation device 180 until the span adjustment screw is in the position opposite the gauge see diagram Secure the Regulation Lever in place with the screw If it...

Page 8: ...as follows 1 Use a regulator with a filter to maintain a constant air supply pressure optimum supply pressure of 6 bar to operate the actuator 2 Completely purge the circuit of air to avoid any forei...

Page 9: ...E S A LAST UPDATE 17 06 2019 UPDATE NUMBER 1 9 Art 5952 00 Art 5952 04 Detail of connection to the transmitter Art 5951 04 Once the connections are completed replace the cover and close using the scre...

Page 10: ...actory 8 1 Zero Setting This sends the stroke start signal 4 mA Rotate the ZERO adjustment wheel clockwise or anti clockwise until the reference lines of the indicator cam match the closed position of...

Page 11: ...d repeat the Span adjustment as many times as necessary Once the equipment has been adjusted tighten the locking screw 8 3 Auto Manual Switch This control is used to switch between Auto and Manual mod...

Page 12: ...Air throttle in pilot valve In the case of actuators with low air capacity this could cause oscillation on the equipment rendering it inoperable In this case use air throttles in outlets OUT1 and OUT2...

Page 13: ...button and the indicator light flashes indicating that regulation begins Observe the aperemeter value the value should be 4 mA if there is deviation can press the button or button adjust the current...

Page 14: ...16 mA to 20 mA around means the feedback signal 75 16 mA position confirmed Module waiting for the feedback signal 100 20 mA position confirm 8 6 7 Feedback signal 100 20 mA position adjusting The va...

Page 15: ...as set out below Disconnect any air or electricity supply Remove the A M Switching regulator from the pilot valve Insert the wire attached to the interior of the cover through the air inlet located i...

Reviews: