Maintenance

30

Owner’s Manual for 60 Hz Air-Cooled Generators

be any electrical problems during generator operation or
when utility power is returned.

Corrosion Protection

Regular scheduled maintenance should be conducted to
perform a visual inspection of the unit for corrosion.
Inspect all metal components of the generator, including
the base frame, brackets, alternator can, the entire fuel
system (inside and outside of the generator), and
fastener locations. If there is corrosion found on
generator components (e.g. regulator, engine/alternator
mounts, fuel plenum, etc.), replace parts as necessary.
Periodically wash and wax the enclosure using
automotive type products. Do not spray the unit with a
hose or power washer. Use warm, soapy water and a soft
cloth. Frequent washing is recommended in salt water/
coastal areas. Spray engine linkages with a light oil such
as WD-40.

Remove From, and Return To 

Service Procedure

Remove From Service

If the generator cannot be exercised monthly, at a
minimum, and will be out of service longer than 90 days,
proceed as follows to prepare the generator for storage:

1.

Start the engine and let it warm up.

2.

Close the fuel shutoff valve in the fuel supply line
and allow the engine to stop.

3.

Once the engine has stopped, set the generator
MLCB (generator disconnect) to OFF (OPEN).

4.

Turn off the utility power to the transfer switch. 

5.

See 

Figure 4-1

. Remove battery charger AC input

T1/Neutral cable (has white sleeve) at controller.

6.

Remove the 7.5 amp fuse from the generator’s
control panel.

7.

Disconnect the battery cables. Remove the
negative cable first.

8.

Drain the oil completely while the engine is still
warm, and then refill the crankcase with oil.

9.

Attach a tag to the engine indicating the viscosity
and classification of the new oil in the crankcase.

10.

Remove the spark plug(s) and spray a fogging
agent into the spark plug(s) threaded openings.
Reinstall and tighten the spark plug(s) to
specification.

11.

Remove the battery and store it in a cool, dry room
on a wooden board.

12.

Clean and wipe down the entire generator.

Return to Service

Proceed as follows to return the unit to service after
storage:

1.

Verify utility power is off.

2.

Check the tag on the engine for oil viscosity and
classification. Drain and refill with proper oil, if
necessary.

3.

Check the state of the battery. Fill all cells of
unsealed batteries to the proper level with distilled
water. DO NOT use tap water. Recharge the
battery to 100% state of charge. Replace the
battery if defective.

4.

Clean and wipe down the entire generator.

5.

Verify that the 7.5 amp fuse is removed from the
generator control panel.

6.

Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected
incorrectly. Install positive cable first.

7.

Reconnect the battery charger AC input T1/Neutral
cable (white sleeve) at controller.

8.

Open the fuel shutoff valve.

9.

Insert the 7.5 amp fuse into the generator control
panel. 

10.

Press the MANUAL button to start the unit. Allow
the unit to warm up for a few minutes.

11.

Complete the Installation Wizard information.

12.

Press the control panel OFF button to stop the unit.

13.

Turn on the utility power to the transfer switch.

14.

Set the control panel to AUTO.

The generator is ready for service.

NOTE: 

The exercise timer and current date and time

must be reset when a battery is dead or has been
disconnected.

WARNING

Explosion. Batteries emit explosive gases.
Always disconnect negative battery cable
first to avoid spark. Failure to do so could
result in death or serious injury.

(000238)

Summary of Contents for 20 kW LP

Page 1: ...uct support lookup Pour le fran ais visiter http www generac com service support product support lookup 000918 Register your Generac product at WWW GENERAC COM 1 888 GENERAC 888 436 3722 000209a WARNI...

Page 2: ...nt checked periodically by an IASD Normal maintenance service and replacement of parts are the responsibility of the owner operator and are not considered defects in materials or workmanship within th...

Page 3: ...e Menu Displays 13 The LCD Panel 13 Menu System Navigation 14 Setting the Exercise Timer 16 Battery Charger 16 Manual Transfer Operation 17 Transfer to Generator Power Source 17 Transfer to Utility Po...

Page 4: ...Table of Contents iv Owner s Manual for 60 Hz Air Cooled Generators Section 5 Troubleshooting Quick Reference Guide Generator Troubleshooting 31 Quick Reference Guide 32...

Page 5: ...e manufacturer strongly recommends that if the operator is also the owner to read the owner s manual and thoroughly understand all instructions before using this equipment The manufacturer also strong...

Page 6: ...rm wiring and connections to unit Failure to follow proper installation requirements could result in death serious injury and damage to equipment or property 000115 WARNING Moving Parts Do not wear je...

Page 7: ...ath or serious injury 000150 DANGER Electrocution Never connect this unit to the electrical system of any building unless a licensed electrician has installed an approved transfer switch Failure to do...

Page 8: ...rged or improperly rated fire extinguishers will not extinguish electrical fires in automatic standby generators 000100a WARNING Consult Manual Read and understand manual completely before using produ...

Page 9: ...with Cover E Exhaust Enclosure J Oil Filter N Fuel Regulator B Main Line Circuit Breaker Generator Disconnect F Oil Fill Cap Dipstick K Oil Drain Hose O Fuel Inlet C Control Panel G Status LED Indica...

Page 10: ...Compartment Battery not supplied J Oil Fill Cap N Sediment Trap B Main Line Circuit Breaker Generator Disconnect F Exhaust Enclosure K Oil Filter O Fuel Regulator C Airbox with Air Cleaner G Status L...

Page 11: ...nded When operated above 77 F 25 C there may be a decrease in engine power See Engine These generators are rated in accordance with UL 2200 Safety Standard for Stationary Engine Generator Assemblies a...

Page 12: ...ication The Emission Control System on this generator consists of the following Fuel Requirements The engine has been fitted with a dual fuel carburetion system The unit will run on natural gas or LP...

Page 13: ...bottom of the new air cooled generators This offers a sleek contoured appearance as well as offering protection from rodents and insects by covering the lifting holes located in the base Requires use...

Page 14: ...General Information 10 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 15: ...d will be locked A set of keys is attached to the intake side of the generator 1 Cut the plastic bag to remove the keys 2 Use the keys to open the lid of the generator NOTE The enclosed keys provided...

Page 16: ...priately sized padlock not included with a shackle long enough to pass through both lock tabs B Figure 3 3 Main Breaker NOTE DO NOT lock out the MLCB during normal generator operation Doing so will co...

Page 17: ...running under generator power utility is lost OFF This button shuts down the engine and prevents automatic operation of the unit MANUAL This button cranks and starts the generator Transfer to standby...

Page 18: ...NG or LP Firmware Update Insert USB Alarm Log Alarm Log Run Log 1 thru 50 1 thru 50 Warning Message s Charger Warning Charger Missing AC Low Battery Battery Problem Exercise Set Error USB Warning Down...

Page 19: ...XXX USB V XXXX Are You Sure Yes or No ESC ENTER ESC ENTER ESC ENTER Select Yes then Press Enter to continue or Press ESCAPE to escape out of updating During update process the Blue Manual light flashe...

Page 20: ...n the fuse is removed Table 3 1 details the exercise information and programming options for all Home Standby Generators Figure 3 8 illustrates the engine speed profile during a typical exercise cycle...

Page 21: ...load Disconnect transfer switch from all power sources prior to manual transfer Failure to do so will result in death or serious injury and equipment damage 002565 A MANUAL Will not transfer to genera...

Page 22: ...or disconnect to ON CLOSED The generator will start automatically when utility source voltage drops below a preset level Loads are transferred to the standby power source after the unit starts Automat...

Page 23: ...mal genera tor voltage output is determined to be low During this cycle the generator controller will display Warming Up on the display screen The generator controller display will show Under Voltage...

Page 24: ...Operation 20 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 25: ...y charger cable Figure 4 1 Disconnecting Battery Charger Cable Performing Scheduled Maintenance It is important to perform maintenance as specified in the Service Schedule for proper generator operati...

Page 26: ...e air filter Clean Check gap Replace spark plugs Inspect adjust valve clearance Inspect clean sediment trap Consult local codes and guidelines Contact the nearest IASD for assistance if necessary Remo...

Page 27: ...he generator to ON CLOSED 4 The system is now operating in automatic mode The main utility disconnect can be turned ON CLOSED Engine Oil Requirements To maintain the product warranty the engine oil sh...

Page 28: ...pter Tighten the filter an additional 3 4 to one full turn 7 Refill the engine with the proper recommended oil See Engine Oil Requirements 8 Press the MANUAL button on the control panel to start the e...

Page 29: ...or service assistance Proper valve clearance is essential for prolonging the life of the engine Check Valve Clearance NOTE The engine should be cool before checking the valve clearance Adjustment is n...

Page 30: ...the Service Schedule Contact an IASD for assistance if necessary Proceed as follows to inspect the battery 1 Press the OFF button to shut down the generator then lift the lid and remove the front pane...

Page 31: ...Sediment Trap The sediment trap removes contaminants moisture and fine particles from gaseous fuels before they enter the fuel regulator Accumulated moisture and particles must be emptied from the sed...

Page 32: ...rankcase with oil 9 Attach a tag to the engine indicating the viscosity and classification of the new oil in the crankcase 10 Remove the spark plug s and spray a fogging agent into the spark plug s th...

Page 33: ...check gap replace plug s as needed 3 Confirm fuel pressure to regulator is 10 12 in water column 19 22 mm Hg for LP and 3 5 7 0 in water column 9 13 mm Hg for natural gas 4 Turn fuel conversion valve...

Page 34: ...ED Unit will not start in AUTO with utility loss Check the LEDs screen for alarms Check oil level and add oil as needed If oil level is correct contact an IASD RPM SENSE LOSS RED Unit will not start i...

Page 35: ...trol panel displays CHECK BATTERY replace the battery BATTERY PROBLEM YELLOW Yellow LED illuminated in any state Check the screen for additional information Contact an IASD CHARGER WARNING YELLOW Yell...

Page 36: ...Troubleshooting Quick Reference Guide 34 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 37: ...Troubleshooting Quick Reference Guide Owner s Manual for 60 Hz Air Cooled Generators 35 This page intentionally left blank...

Page 38: ...Troubleshooting Quick Reference Guide 36 Owner s Manual for 60 Hz Air Cooled Generators This page intentionally left blank...

Page 39: ......

Page 40: ...ights reserved Specifications are subject to change without notice No reproduction allowed in any form without prior written consent from Generac Power Systems Inc Generac Power Systems Inc S45 W29290...

Reviews: