4000EXL Extended Life Generator
11
2.
Unplug charger from unit and wall outlet when
generator is being started and while in operation.
3.
Keep charger plugged in when generator is not in use
to prolong battery life.The charger has a built in float
equalizer and will not overcharge battery, even when
plugged in for an extended period of time.
IMPORTANT: See “Battery Maintenance” on page 16 for
additional information.
RECEPTACLES
120 Volt AC, 15 Amp Receptacles
Each of these outlets is protected against overload by
15 Amp push-to-reset type circuit breakers (Figure 9).
Use each outlet to operate 120 Volt, 60 Hz, single phase
loads requiring 1,800 (1.8 kW) watts at 15 Amps of current.
120/240 Volt AC, 20 Amp Locking
Receptacle
Use a NEMA L14-20 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volts at 20 Amps (or greater)
(Figure 10).You can use the same 4-wire cord if you plan to
run a 120 Volt load.
This receptacle powers 120/240 Volt AC, 60 Hz, single
phase loads requiring up to 2,000 watts of power at
16.7 Amps for 120 Volts; 4,000 watts of power (4.0 kW) at
16.7 Amps for 240 Volts.The outlet is protected by a
20 Amp push-to-reset circuit breaker.
Figure 9 — 120 Volt AC, 15 Amp Duplex Receptacle
• NEVER attempt to power a device requiring more amperage
than generator or receptacle can supply.
• DO NOT overload the generator. See “Don’t Overload
Generator”.
Receptacles may be marked with rating value greater
than generator output capacity.
CAUTION
Figure 10 — 120/240 Volt AC, 20 Amp Receptacle
4-Wire Cord Set
240V
120V
120V
W (Neutral)
X (Hot)
Y (Hot)
NEMA L14-20
Ground (Green)