Automatic Standby Generator Owner’s Manual
3.6.2— Transfer Back to Utility Power Source
When utility power has been restored, transfer back to utility source and shut down the generator. To manually transfer back to utility power and
shut down the generator:
1. Set the Main Circuit Breaker (Generator Disconnect) to its OFF (OPEN) position.
2. Allow the engine to run for 2 minutes at no-load to stabilize the internal temperatures.
3. Press the Control Panel OFF button. The engine should shut down.
4. Ensure that utility power supply to the transfer switch is turned off.
5. Use the manual transfer handle inside the transfer switch to move the main contacts back to their UTILITY posi-
tions (loads connected to the utility power source).
6. Turn on the utility power supply to the transfer switch using the means provided.
7. Press the Control Panel AUTO button.
3.7 — Side Compartment
Local codes may require this compartment to be locked. A hasp is provided so the owner/operator can secure the compartment with his or her
own padlock. Check local codes for side compartment locking requirements.
Figure 3-5: Open Side Compartment
3.7.1— Main Circuit Breaker (Generator Disconnect)
This is a 2-pole breaker rated according to relevant specifications.
3.7.2— LED Indicator Lights
•
Green LED “Ready” light is on when utility is present and the Control Panel button is in the AUTO position. This also indicates when the gen-
erator is running.
•
Red LED “Alarm” light is on when the generator is OFF or a fault is detected and means contact your authorized servicing dealer.
•
Yellow LED “Maintenance” light. Note: Yellow LED may be on at the same time as either the Red or Green LEDs.
120V GFCI OUTLET
15 Amp OUTLET BREAKER
MAIN CIRCUIT BREAKER
LED INDICATOR LIGHTS
Summary of Contents for 6244
Page 4: ...iii This page intentionally left blank ...
Page 14: ...10 Automatic Standby Generator Owner s Manual This page intentionally left blank ...
Page 22: ...18 Automatic Standby Generator Owner s Manual This page intentionally left blank ...
Page 32: ...28 Automatic Standby Generator Owner s Manual This page intentionally left blank ...
Page 35: ......
Page 40: ...iii Esta página se ha dejado en blanco intencionalmente ...
Page 71: ......
Page 76: ...iii Page laissée en blanc intentionnellement ...
Page 107: ......