Installation and Operating Instructions 

MANUAL TRANSFER SWITCH MODELS 6335 AND 6382 

 

NOTE TO INSTALLER

:  Please leave this guide with the consumer for future reference. READ THIS MANUAL IN ITS ENTIRETY BEFORE ATTEMPTING TO INSTALL THIS EQUIPMENT.   

WARNING: 

 Generac

®

 transfer switches should be installed by a professional electrician familiar with electrical wiring and codes, and experienced in working with generators.  Generac 

accepts no responsibility for accidents, damages or personal injury caused by incorrect installation.  This transfer switch is intended for surface mounting OUTDOORS.  Our transfer 

switches are UL listed to UL Standard 1008 and meet the criteria of National Electrical code Article 702.6 for Optional Standby Systems.  

CAUTION:  

If using the generator and transfer 

switch for larger appliances, such as electric water heaters, clothes dryers, electric ranges and small air conditioners, check the labels on the appliances to be sure they do NOT exceed 
the rating of the generator.  No appliance should have an amperage rating that exceeds the individual breaker rating in the transfer switch.  

CALIFORNIA PROPOSITION 65 WARNING

:  

Engine exhaust and some of its constituents are known to the State of California to cause cancer, birth defects and other reproductive harm.  This product may contain or emit chemicals 
known to cause cancer, birth defects and other reproductive harm. 

 

 

Thank you for purchasing a Generac Manual Transfer switch to safely connect a portable 

generator to the load center in your home or business (single phase only) for standby power 

applications.  Product features include: 

 

 

Generator and Utility Mains mechanically interlocked preventing utility or generator power back feed. 

 

Full branch circuit protection with Siemens

®

 circuit breakers. 

 

12 gauge High Corrosion-resistant aluminum cabinet. 

 

Ample ground and neutral termination positions for all branch circuits. 

 

Extra spaces for branch circuit breakers. 

 

Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits. 

 

Accepts a Switched Neutral Kit (Model 6297).  See Note on Neutral Bonded Generators found above 
Table 1. 

 

 

 

Description: 

This unit is a combination indoor/outdoor transfer switch and distribution panel.  
It can be used as service entrance equipment for 200 Amp services.  In addition 
to being a transfer switch, this unit provides additional circuits for outdoor 
applications such as air conditioner compressors, sewage lift pumps, boat 
docks, outbuildings, garages, pump houses, barns and the like.  These 200 amp 

series models will accommodate 12 single pole circuits.   

 

This transfer switch is made up of five basic elements: 

1.

 

200 amp rated Utility Main Breaker 

2.

 

Generator Main Breaker 

3.

 

A 30 or 50 amp 125/250 volt inlet pre-wired to the generator breaker 

4.

 

A mechanical safety interlock that prevents both Mains from being 
“ON” at the same time 

5.

 

A set of sub-feed lugs to handle cable up to 4/0 AWG to feed the 
house Main panel. 

 

Tools and Items Needed for Installation:  

 

1/4" and 11/32 nut drivers 

 

Straight blade and Phillips screwdriver 

 

Large Allen wrench Set 

 

Electric drill 

 

Wire cutter/stripper 

 

Anchors and screws to mount switch to wall 

 

Power Cord to connect generator to switch 

 

Compatible Circuit Breaker Types: 

 

Siemens/Murray QT, QPH, HQP, QPF (GFCI), QPHF, QFP, QE, QEH, 

QAF (Arc Fault), QP (Surge Protector) 

 

Cutler-Hammer Series BD, BR, BQ, GFC 

 

Challenger Type A, C, HAGF 

 

Square D Series HOM (Homeline) 

 

GE Series THQL 

 

CAUTION

:  If this transfer switch is used as the main service disconnect, it is imperative that all circuit breakers in the transfer switch AND the Main Load Center in the house 

be turned OFF when running the system from the generator.  Then, turn on only the breakers that the generator can handle at any one time.  Check the generator “continuous” 
wattage rating to determine the total wattage of connected load.  It may be necessary as well as desirable to turn ON and OFF different loads/breakers as needed during an 
actual power outage. 

Summary of Contents for GenTran 6335

Page 1: ...all branch circuits Extra spaces for branch circuit breakers Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits Accepts a Switched Neutral Kit Model 6297 See Note on Neutral Bonded Generators found above Table 1 Description This unit is a combination indoor outdoor transfer switch and distribution panel It can be used as service entrance equipment for 200 Am...

Page 2: ...umber of circuits may be reduced from the number shown STEP 1 INSTALLATION PROCEDURE HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY FOLLOW PROPER INSTALLATION OPERATION AND MAINTENANCE PROCEDURES TO AVOID HAZARDOUS VOLTAGES TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING INSTALLATION 1 Although this transfer swit...

Page 3: ...d Center up to the continuous wattage rating of your generator If the Generator Main breaker trips you have overloaded the generator Some circuit breakers must be turned OFF to avoid damage to the generator or loads being connected Transferring from Generator Power to Utility Power 1 On the Transfer switch turn OFF Generator MAIN breaker and turn ON Utility MAIN breaker To do this slide the interl...

Page 4: ...u produit L alimentation de la génératrice et de l installation de service sont mécaniquement verrouillées pour empêcher que l installation de service et la génératrice soient réalimentées Protection totale du circuit de dérivation avec des disjoncteurs Siemens Armoire en aluminium hautement anticorrosive calibre 12 Positions terminales de masse et de neutre suffisantes pour tous les circuits de d...

Page 5: ...érentiels de fuite à la terre GFCI les interrupteurs d amorçage d arc AFCI ou les disjoncteurs de protection contre les surtensions sont utilisés dans le centre électrique le nombre maximum de circuits indiqué dans le tableau ci dessus sera réduit De même si l on utilise des disjoncteurs de plus de 50 ampères en tant que disjoncteurs d artère secondaire le nombre maximum des disjoncteurs sera égal...

Page 6: ...s dans le manuel du propriétaire de la génératrice fourni par le fabricant 6 Mettez en MARCHE le disjoncteur de la GÉNÉRATRICE dans le centre électrique 7 Mettez en MARCHE les disjoncteurs individuels du commutateur de transfert manuel et du centre de distribution principal jusqu à atteindre la puissance nominale continue de la génératrice Si le disjoncteur de la génératrice se déclenche vous avez...

Page 7: ...el servicio eléctrico se encuentran entrelazados mecánicamente para evitar la retroalimentación eléctrica del servicio eléctrico o del generador Protección total del circuito derivado con el disyuntor Siemens Gabinete de aluminio de calibre 12 con alta resistencia a la corrosión Conexión a tierra suficiente y posiciones de terminación neutral para todos los circuitos derivados Espacios adicionales...

Page 8: ... GFCI interruptores por falla de arco o disyuntores protectores contra sobrecargas en el centro de energía éstos reducirán la cantidad máxima de circuitos del número que aparece en la tabla anterior Asimismo si se utilizan disyuntores superiores a los 50 amps como disyuntores de subalimentación también se reducirá la cantidad máxima de disyuntores de circuito Comuníquese con su instalador o conces...

Page 9: ...s procedimientos descritos en el manual del usuario del generador provisto por el fabricante 6 Encienda el disyuntor PRINCIPAL DEL GENERADOR en el centro de energía 7 Encienda los disyuntores individuales en un interruptor de transferencia y el centro de carga principal hasta la calificación de vataje continuo de su generador Si se activa el disyuntor principal del generador se ha sobrecargado el ...

Reviews: