NOTE ON NEUTRAL BONDED GENERATORS:  

Some portable generators are intended for use on jobsites and are subject to OSHA regulations for GFCI protection on all receptacles. 

These "contractor grade" generators have their neutral wire bonded to the ground wire to pass OSHA inspection. When connected to a transfer switch, this may cause nuisance tripping 
of the generator GFCI breaker.  When using a neutral bonded generator to power a house or building through a transfer switch, consult the generator manufacturer or local authorized 

service dealer to determine if the neutral bond wire on the generator can be disabled without voiding the warranty.  If it can be disabled, then no modifications to your transfer switch 
installation are needed.  If the neutral bond cannot be removed or voids the warranty, you must install a Switched Neutral Kit (SNK, Generac model 6297) accessory with your transfer 
switch.  NOTE:  Removal of the neutral bond should be performed by an authorized generator service dealer or qualified electrician.  If the neutral bond is removed, the generator will no 
longer pass OSHA inspection for job sites.

 

 

TABLE 1 - SPECIFICATIONS

 

MODEL: 

6382 

6335 

UTILITY MAIN breaker, Included  

200 Amp 

200 Amp 

GEN MAIN breaker, included 

30 Amp 

50 Amp 

Max Load per Circuit 

As marked 

As marked 

Max Load on Generator 

30 Amp 

50 Amp 

Max Watts @ 250 Volt 

7500 12,500 

Max Watts @ 125 Volt 

7500 12,500 

Max 1-pole Circuits * 

12 12 

Max 2-pole Circuits * 

6 6 

NEMA Configuration of Power Inlet 

L14-30 CS6365 

Voltage 

125/250 Volts 

125/250 Volts 

NEMA Type Enclosure  

3R – Outdoor  

3R – Outdoor  

Phase 

1 1 

Minimum Gauge Cord Size 

10/4 AWG 

6/4 AWG 

*NOTE:  If Ground Fault Circuit Interrupting (GFCI) breakers, Arc-Fault breaker or surge protecting circuit breakers are used in the transfer switch, they will reduce the 
maximum number of circuits from the number shown in the table above.  Also if circuit breakers larger than 50 amps are used as sub-feed breakers, the maximum number of 
circuit breakers will also be reduced.  Contact your local installer or dealer for more information on GFCI, Arc-Fault and Surge Protecting circuit breakers.  

Because GFCI and 

AFCI circuit breakers can take up more than one space, the overall maximum number of circuits may be reduced from the number shown.  

 

STEP 1:  INSTALLATION PROCEDURE: 

  HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY.  FOLLOW PROPER INSTALLATION, 

OPERATION AND MAINTENANCE PROCEDURES TO AVOID HAZARDOUS VOLTAGES.  

TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING INSTALLATION

.

  

1.

 

Although this transfer switch can be installed above, below or on either side of the utility meter socket, the preferred location is to the RIGHT of the 

meter socket since the location of the lugs for the Utility Main are on 
the Left side of the transfer switch.  Knockouts (KO) are provided 
only in the bottom of the enclosure.  However, since the enclosure is 
aluminum, it is easy to cut in the desired knockout.  If the KO is cut 
in above the live terminals of the circuit breakers, a watertight hub 
should be used.  NOTE:  If a 2” KO is cut in the side of the Transfer 

switch enclosure, the dead front panel may need to be “notched” to 
clear the 2” fittings.  The back of the KO must be 3/8” from the rear 
of the enclosure. 

2.

 

Loosen the thumb screw from the cover of the transfer switch, and 
slide the cover down to remove.  The thumb screw stays attached to 

the cover. 

3.

 

Remove the two screws from the bottom of the dead front.  When 
the cover is pulled forward, the snap-in closing plates will fall out.  
Set the front cover and dead front aside for reinstallation after wiring. 

4.

 

The mounting holes in the back of the transfer switch are on 16” 

centers so they could line up on your studs if desired.  We 
recommend using all four holes to mount the enclosure. 

5.

 

Select the bottom center 2” KO to exit to the Main distribution panel.  
Terminate the LOAD wires in the landing lugs on the bottom of the 
bus assembly, one to the Neutral lug and one to the Ground lug on 

the right side of the enclosure.   

6.

 

Terminate wires from the meter socket into the utility Main breaker 
on the left side, and the Neutral into the unused lug on the insulated 
neutral bar. 

7.

 

Plug in and wire any additional branch circuit breakers in the spaces 
provided.  Installer will need to remove any hold-down strap to insert 

additional circuit breakers.  Re-install hold-down strap after breakers 
are inserted. 

8.

 

Reinstall dead front cover and interlock mechanism if removed earlier.  Fill any unused spaces in the dead front with the closing plates provided. 

9.

 

Reinstall cover. 

Summary of Contents for GenTran 6335

Page 1: ...all branch circuits Extra spaces for branch circuit breakers Subfeed lugs provided to feed additional downstream panels or to expand beyond 16 circuits Accepts a Switched Neutral Kit Model 6297 See Note on Neutral Bonded Generators found above Table 1 Description This unit is a combination indoor outdoor transfer switch and distribution panel It can be used as service entrance equipment for 200 Am...

Page 2: ...umber of circuits may be reduced from the number shown STEP 1 INSTALLATION PROCEDURE HAZARDOUS VOLTAGES ARE PRESENT INSIDE TRANSFER SWITCH ENCLOSURES THAT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY FOLLOW PROPER INSTALLATION OPERATION AND MAINTENANCE PROCEDURES TO AVOID HAZARDOUS VOLTAGES TURN OFF THE MAIN CIRCUIT BREAKER IN THE LOAD CENTER BEFORE STARTING INSTALLATION 1 Although this transfer swit...

Page 3: ...d Center up to the continuous wattage rating of your generator If the Generator Main breaker trips you have overloaded the generator Some circuit breakers must be turned OFF to avoid damage to the generator or loads being connected Transferring from Generator Power to Utility Power 1 On the Transfer switch turn OFF Generator MAIN breaker and turn ON Utility MAIN breaker To do this slide the interl...

Page 4: ...u produit L alimentation de la génératrice et de l installation de service sont mécaniquement verrouillées pour empêcher que l installation de service et la génératrice soient réalimentées Protection totale du circuit de dérivation avec des disjoncteurs Siemens Armoire en aluminium hautement anticorrosive calibre 12 Positions terminales de masse et de neutre suffisantes pour tous les circuits de d...

Page 5: ...érentiels de fuite à la terre GFCI les interrupteurs d amorçage d arc AFCI ou les disjoncteurs de protection contre les surtensions sont utilisés dans le centre électrique le nombre maximum de circuits indiqué dans le tableau ci dessus sera réduit De même si l on utilise des disjoncteurs de plus de 50 ampères en tant que disjoncteurs d artère secondaire le nombre maximum des disjoncteurs sera égal...

Page 6: ...s dans le manuel du propriétaire de la génératrice fourni par le fabricant 6 Mettez en MARCHE le disjoncteur de la GÉNÉRATRICE dans le centre électrique 7 Mettez en MARCHE les disjoncteurs individuels du commutateur de transfert manuel et du centre de distribution principal jusqu à atteindre la puissance nominale continue de la génératrice Si le disjoncteur de la génératrice se déclenche vous avez...

Page 7: ...el servicio eléctrico se encuentran entrelazados mecánicamente para evitar la retroalimentación eléctrica del servicio eléctrico o del generador Protección total del circuito derivado con el disyuntor Siemens Gabinete de aluminio de calibre 12 con alta resistencia a la corrosión Conexión a tierra suficiente y posiciones de terminación neutral para todos los circuitos derivados Espacios adicionales...

Page 8: ... GFCI interruptores por falla de arco o disyuntores protectores contra sobrecargas en el centro de energía éstos reducirán la cantidad máxima de circuitos del número que aparece en la tabla anterior Asimismo si se utilizan disyuntores superiores a los 50 amps como disyuntores de subalimentación también se reducirá la cantidad máxima de disyuntores de circuito Comuníquese con su instalador o conces...

Page 9: ...s procedimientos descritos en el manual del usuario del generador provisto por el fabricante 6 Encienda el disyuntor PRINCIPAL DEL GENERADOR en el centro de energía 7 Encienda los disyuntores individuales en un interruptor de transferencia y el centro de carga principal hasta la calificación de vataje continuo de su generador Si se activa el disyuntor principal del generador se ha sobrecargado el ...

Reviews: