APPLICATION
& ENGINEERING DATA

Rating definitions - Standby: Applicable for supplying emergency power for the duration of the utility power outage.  No overload capability is available for this rating.  (All ratings in accordance with BS5514, 
ISO3046 and DIN6271).  (All ratings in accordance with BS5514, ISO3046, ISO8528 and DIN6271).

COMMERCIAL 130 kW

GENERATOR SPECIFICATIONS

TYPE ................................................................................................................Synchronous
ROTOR INSULATION ................................................................................................ Class H
STATOR INSULATION .............................................................................................. Class H
TOTAL HARMONIC DISTORTION ...............................................................................<3.5%
TELEPHONE INTERFERENCE FACTOR (TIF) .................................................................. <50

ALTERNATOR OUTPUT LEADS 3 PHASE ....................................................................4 wire
BEARINGS...........................................................................................................Sealed Ball
COUPLING ...........................................................................................................Gear  Drive
LOAD CAPACITY (STANDBY RATING) ..................................................................... 130 kW

EXCITATION SYSTEM ...........................................................................................Brushless

NOTE:   Generator rating and performance in accordance with 
ISO8528-5, BS5514, SAE J1349, ISO3046, and DIN6271 standards.

GENERATOR FEATURES

 

Revolving field heavy duty generator

 

Quiet drive coupling

 

Operating temperature rise 120 °C above a 40 °C ambient

 

Insulation is Class H rated at 150 °C rise

 

All prototype models have passed three phase short circuit testing

VOLTAGE REGULATOR

TYPE ................................................................................................................... Full  Digital
SENSING..................................................................................................................3 Phase
REGULATION ............................................................................................................± 1/4%
FEATURES............................................................................ Built into H-100 Control Panel
 V/F 

Adjustable

 

Adjustable Voltage and Gain

CONTROL PANEL FEATURES

 

TWO FOUR LINE LCD DISPLAYS READ:

 

  • Voltage (all phases) 

• Current (all phases)

 

  • Power factor 

• kW

 

  • kVAR 

• Transfer switch status

 

  • Engine speed 

• Low fuel pressure

 

  • Run hours 

• Service reminders

 

  • Fault history 

• Oil pressure

 

  • Coolant temperature 

• Time and date

 

  • Low oil pressure shutdown 

• High coolant temperature shutdown

  

• 

Overvoltage 

• 

Overspeed

 

  • Low coolant level 

• ATS selection

 

  • Not in auto position (flashing light) 

• Exercise speed

 

 

 

INTERNAL FUNCTIONS:

  

• 

I2T function for alternator protection from line to neutral and line to line short circuits

 

  • Emergency stop

 

  • Programmable auto crank function

 

  • 2 wire start for any transfer switch

 

  • Communicates with the Generac HTS transfer switch

 

  • Built-in 7 day exerciser

 

  • Adjustable engine speed at exerciser

 

  • RS232 port for GenLink

®

 control

 

  • RS485 port remote communication

 

  • Canbus addressable

 

  • Governor controller and voltage regulator are built into the master control board

 

  • Temperature range -40 °

C to 70 °C

ENGINE SPECIFICATIONS

MAKE ......................................................................................................................  Generac

MODEL ......................................................................................................................V Type

CYLINDERS ..................................................................................................................... 10

DISPLACEMENT ..................................................................................................... 6.8  Liter

BORE............................................................................................................................. 3.55

STROKE ........................................................................................................................ 4.17

COMPRESSION RATIO ................................................................................................... 9:1

INTAKE AIR SYSTEM ..............................................................................Naturally Aspirated

VALVE SEATS ........................................................................................................ Hardened

LIFTER TYPE ......................................................................................................... Hydraulic

GOVERNOR SPECIFICATIONS

TYPE .....................................................................................................................Electronic

FREQUENCY REGULATION ...............................................................................Isochronous

STEADY STATE REGULATION .................................................................................± 0.25%

All functions are factory preset.

Individual parameter adjustments can be made via GenLink

®

.

ENGINE LUBRICATION SYSTEM

OIL PUMP ..................................................................................................................... Gear

OIL FILTER ...................................................................................Full flow spin-oncartridge

CRANKCASE CAPACITY ......................................................................................... 5 Quarts

ENGINE COOLING SYSTEM

TYPE ......................................................................................................................... Closed

WATER PUMP ......................................................................................................Belt driven

FAN SPEED .................................................................................................................. 1950

FAN DIAMETER ..................................................................................................... 26 inches

FAN MODE .................................................................................................................. Puller

FUEL SYSTEM

FUEL TYPE ................................................................................Natural gas, propane vapor

CARBURETOR .....................................................................................................Down  Draft

SECONDARY FUEL REGULATOR ........................................................................... Standard

FUEL SHUT OFF SOLENOID .................................................................................. Standard

OPERATING FUEL PRESSURE .......................................................................11” - 14” H2O

ELECTRICAL SYSTEM

BATTERY CHARGE ALTERNATOR .....................................................................12V 30 Amp

STATIC BATTERY CHARGER ...............................................................................12V 2 Amp

RECOMMENDED BATTERY .................................................................Group 24F, 525 CCA

SYSTEM VOLTAGE.................................................................................................. 12 Volts