MMG185 Generac Specifications Continued:  

Manufactured by Magnum Power Products LLC., a wholly owned subsidiary of Generac Power Systems, Inc.                                                                                                 

                                                                                   Phone: 800-926-9768  Fax: 920-361-2214  www.m-p-llc.com  

 

Page 2 of 4 

4/12

 

o

 

Six LED indicators w/ lamp test 

 

Alarm / Fault (Red)  

 

Ready / Manual (Red) 

 

Running (Green) 

 

Warning (Yellow) 

 

Ready / Auto (Green) 

 

Supplying Load (Green) 

 

Push buttons for easy operation 

o

 

Manual or Auto Start 

o

 

Engine Start or Stop 

o

 

Alarm Cancel & Fault Reset 

o

 

Scrolling Arrows for Diagnostic Information 

 

System kW output display 

 

Line output & frequency display 

 

Engine diagnostic display 

 

Oil pressure 

 

Engine temperature 

 

Fuel level 

 

Battery 

 

System hours 

 

Running hours 

 

kW hours 

 

Time to service 

o

 

Alarm list – warnings / shutdowns are date & time stamped 

 

Fuel level: warning – 15%; shutdown – 5%  

 

Overspeed protection: shutdown – 115% 

 

Oil pressure: warning – 25 psi; shutdown – 20 psi 

 

Coolant temperature: warning – 220°F; shutdown – 230°F 

 

Battery voltage: over – 15VDC; under – 11VDC 

 

Generator over voltage: warning – 110%; shutdown – 111% 

 

Generator under voltage: warning – 87%; shutdown – 86% 

 

Generator over frequency: warning – 105%; shutdown – 110% 

 

Generator under frequency: warning – 95%; shutdown – 90% 

 

Over current shutdown

 

ELECTRICAL CONTROLS 

 

Remote start / stop contacts located next to lug box 

 

Lockable control box door with diagnostics window 

 

Lockable lug box with safety switch 

o

 

Trips main breaker when lug door is opened 

Disables voltage regulator

 

 

Cable entry guides to the lug box 

o

 

Restricts access of foreign objects 

 

Output ground connection lug inside lug box 

 

700A main breaker with shunt trip 

 

Convenience receptacles with individual breakers (restricted use in high wye mode) 

o

 

(2) 120V 20 Amp GFCI duplex outlets (Nema 5-20R type) 

o

 

(3) 125 / 250V 50 Amp, 3 pole, 4 wire twistlock (Non-Nema 6369) 

 

Panel mounted rheostat for voltage adjustment - +/- 10% 

 

1000 CCA wet cell battery

 

 