Mobile Generator – MMG320 Specifications 

ENGINE  

 

John Deere

®

 RG6090HF485 - turbocharged, diesel engine 

o

 

Prime - 384 hp @ 1800 rpm 

o

 

Standby - 422 hp @ 1800 rpm 

o

 

6 cylinder 

o

 

9.0 L displacement 

o

 

Tier III approved 

 

Steel, single wall fuel tank 

o

 

459 gal. capacity 

o

 

24 hr. run time – full load  

o

 

Fuel tank built into skid of generator set 

 

Fuel consumption at prime: 

o

 

100% - 17.9 gph (67.8 Lph) 

o

 

75% - 13.4 gph (50.7 Lph) 

o

 

50% - 9.0 gph (34.1 Lph) 

 

Cooling system capable of operating at 120°F ambient 

 

Low coolant shutdown 

 

Radiator and oil drains plumbed to exterior 

 

Rubber vibration dampers isolate engine/generator from frame 

 

In-line engine block heater 

 

Disposable air filter - paper element 

 

Air filter restriction indicator mounted on control panel 

 

60 Hz engine/generator  

 

Electronic isochronous governing

 

GENERATOR 

 

Marathon Electric

®

 

o

 

Brushless 

o

 

4 pole 

o

 

Class H insulation 

 

Voltage regu/- 1% with Marathon SE350 Voltage Regulator 

SYSTEM OUTPUT 

 

Link / Reconnect Board: 

o

 

Three phase – 120 / 208V Low Wye 

o

 

Three phase – 277 / 480V High Wye 

 

278 kW / 348 kVA – standby, three phase 

 

256 kW / 320 kVA – prime, three phase  

SYSTEM CONTROLS 

 

Microprocessor-based controller 

o

 

Backlit, 128x64 pixel resolution display 

o

 

-40°F to 185°F operating temperature range 

o

 

Thermostatically controlled LCD heater 

 
 
 

320

MOBILEPO

WER

MOBILEPO

WER

Summary of Contents for Mobile Power MMG320

Page 1: ...at 120 F ambient Low coolant shutdown Radiator and oil drains plumbed to exterior Rubber vibration dampers isolate engine generator from frame In line engine block heater Disposable air filter paper element Air filter restriction indicator mounted on control panel 60 Hz engine generator Electronic isochronous governing GENERATOR Marathon Electric o Brushless o 4 pole o Class H insulation Voltage r...

Page 2: ...25 psi shutdown 20 psi Coolant temperature warning 220 F shutdown 230 F Battery voltage over 15VDC under 11VDC Generator over voltage warning 110 shutdown 111 Generator under voltage warning 87 shutdown 86 Generator over frequency warning 105 shutdown 110 Generator under frequency warning 95 shutdown 90 Over current shutdown ELECTRICAL CONTROLS Remote start stop contacts located next to lug box Lo...

Page 3: ...ated on outside of enclosure Central lifting point Multi lingual operating safety decals Document holder with operating manual including AC DC wiring diagrams TRAILER DOT approved tail side brake and directional lights o Recessed rear lights Transportation tie downs Safety chains with spring loaded safety hooks 3 lunette ring hitch 2 8000 lb axles with electric brakes 15000 lb tongue jack with foo...

Page 4: ...le phase 120 240V Zig Zag Three phase 120 208V Low Wye Three phase 277 480V High Wye Three phase 120 240V Delta Dedicated voltage configurations Cam locks SYSTEM CONTROLS OPTIONS Auxiliary strobe audible indication for soft hard alarm conditions COOLANT OPTIONS 60 40 Coolant cold weather applications ENCLOSURE OPTIONS Fire extinguisher Interior cabinet light Control panel light FUEL TANK OPTIONS 3...