PWRview for PWRcell Set-up Guide

1

RGM Accessory Kit Installation Manual

PCRGM1

Kit Contents

Tools Required

Phillips Head Screwdriver

Flat Head Screwdriver

Flush Cutter / Wire Cutter

Instructions

NOTE: 

Competent,  qualified  personnel  should  install,

operate,  and  service  this  equipment.  Strictly  comply  to

local,  state,  and  national  electrical  and  building  codes.

When  using  this  equipment,  comply  with  regulations

established by the National Electrical Code (NEC), CSA

Standard; the Occupational Safety and Health Adminis

-

tration (OSHA), or the local agency for workplace health

and safety.

1.

Initiate  an  inverter  shutdown  by  pressing  the  red

Shutdown button on the inverter front control panel. 

2.

Allow DC voltage to drop below 10VDC.

3.

Open all PWRcell DC Disconnects and verify DC

voltage  reported  on  LCD  screen  has  dropped  to

below 10VDC.

4.

Disconnect AC Grid source to inverter and wait for

Inverter LCD screen to turn off.

5.

Ensure all sources of AC and DC Power are dis

-

connected.

6.

Open  the  inverter  front  cover  to  horizontal  and

push inward to lock in the open position.

7.

Use a Phillips Head screwdriver to remove the wir

-

ing compartment cover (5 screws total).

8.

Locate  the  4  standoffs  on  the  rear  sheet  metal

panel.

9.

Place  mounting  plate  over  the  standoffs  and

secure with the included mounting screws.

10.

Follow wiring diagram on the backside to complete

PWRView meter install.

11.

Clip PWRView meter onto the mounting plate.

12.

Replace  dead-front  over  the  inverter  wiring  com

-

partment and tighten screws.

13.

Close front cover.

14.

Power on inverter.

15.

Follow  install  verification  steps  on  next  page  to

confirm everything is in working order.

Quantity

Description

1

PWRView Meter

2

Current Transformers

1

Voltage Cable

1

Mounting Plate

4

Mounting Screws

4

Cable Ties

(000686)

DANGER

Electrocution. Never touch terminals when 
inverter and PWRcell DC disconnects are ON. 
Doing so could result in death or serious injury. 

(000188)

DANGER

Electrocution. Do not wear jewelry while 
working on this equipment. Doing so will 
result in death or serious injury.

(000191)

DANGER

Automatic start-up. Disconnect utility power and 
render unit inoperable before working on unit. 
Failure to do so will result in death or serious injury.

(000187)

WARNING

Electrocution. Potentially lethal voltages are generated
by this equipment. Render the equipment safe before
attempting repairs or maintenance. Failure to do so
could result in death or serious injury.

011165