Installing PWRcell Inverter
Installation Manual for Generac PWRcell Inverter
11
Section 4: Installing PWRcell Inverter
Mounting the Inverter
(000641)
WARNING
Equipment damage. Mount inverter to a strong, stable surface.
Never mount to drywall, plaster, or other non-structural wall
treatments. Failure to mount inverter to a strong, stable surface
could result in equipment or property damage.
1.
Verify mounting location adheres to the following
requirements:
•
Inverter must be mounted upright on a vertical wall.
•
Mounting surface must be a strong, stable surface.
Never mount to drywall, plaster or non-structural
building finishes.
•
Fasteners must engage with at least two studs or
other structural members.
•
Never obstruct intake or exhaust vents.
•
Never allow water to enter intake or exhaust vents.
•
See
. Observe all mounting clearances.
009989
A
F
B
G
H
I
C
D
E
K
L
J
Figure 4-1. Mounting Clearances
A
4 in (101.6 mm)
G
24.5 in (622.3 mm)
B
19.25 in (489 mm)
H
8 in (203.2 mm)
C
8 in (203.2 mm)
I
28.5 in (723.9 mm)
D
20 in (508 mm)
J
28 in (711.2 mm)
E
8.5 in (215.9 mm)
K
36 in (914.4)
F
8 in (203.2 mm)
L
Floor
2.
Verify fasteners are suitable for the mounting
surface and can adequately secure the inverter to
the wall. See
3.
See
. Secure bracket (A) to mounting
surface. Fasteners must engage at least two studs
or other structural members.
NOTE:
Mounting slots (B) accommodate different stud
spacings.
A
B
009990
Figure 4-2. Installing Mounting Bracket
4.
See
. Insert bracket tabs (C) into
inverter body slot (D).
C
D
009991
Figure 4-3. Mounting Inverter onto Bracket
5.
See
. Secure inverter to wall with two
fasteners through mounting holes (E).
E
009992
Figure 4-4. Mounting Holes