Electrical Connections
Installation Manual for Generac PWRCell Inverter
19
Connecting CTs to the Inverter
•
See
. Connect CTs to the inverter using
a RJ-45 connector and Category 5 (Cat 5) Ethernet
cable.
•
CT input jack (H) is a double-stacked RJ-45 jack.
Either the top or bottom jack may be used.
NOTE:
Connect CTs to the CT input jack in the middle of
the wiring compartment. Do not connect CTs to the
Ethernet jack. Do not connect the Internet to the CT input
jack. See
Generac PWRcell Inverter Wiring
:
010001
H
I
J
K
L
Figure 5-8. Accessory Ports
H
CTs RJ-45 jack
I
ATS (Automatic Transfer Switch) RJ-45 jack
J
REbus Beacon USB-B
K
Authorized Generac personnel only
L
External safety shutdown switch terminals
•
See
. Connect CT leads to RJ-45
Breakout Adapter (M), using the wire coding shown
in
010002
M
Figure 5-9. RJ-45 Breakout Adapter
NOTE:
RJ-45 Breakout Adapter is included in the
Generac PWRcell Kit.
NOTE:
If the RJ-45 Breakout Adapter is not available,
the CT leads can be wired to a Cat 5 cable.
Table 5-8. CT Pinout
Pin
Wire Color
(T-568A)
Wire Color
(T-568B)
Value
1
White/Green
White/Orange
CT3+
2
Green
Orange
CT3-
3
White/Orange
White/Green
CT2+
4
Blue
Blue
CT1+
5
White/Blue
White/Blue
CT1-
6
Orange
Green
CT2-
7
White/Brown
White/Brown
Not Used
8
Brown
Brown
Not Used
CT Calibration
•
Install CTs before powering ON the inverter.
•
The inverter automatically detects and calibrates
CTs when turned ON.
•
Once CTs are detected and calibrated, a utility pole
symbol will appear on the lower right corner of the
home screen power flow diagram.
•
If manual CT calibration is required, set
CalOverride to 1. The CalOverride setpoint is
accessible through the Mod. Settings menu via the
inverter device page. See
for more
information.
– CT1 must be connected to Line 1.
– CT2 must be connected to Line 2.
– CT3 must be connected to line 3 (for three phase
applications).
– All CTs must be pointed such that positive cur-
rent defined by the arrow of the CT is pointed
towards the grid.
Table 5-9. CT Setpoints
Setpoint
Behavior
Default
Units
C
•
Overrides automatic CT detection.
•
When set to 0, the inverter automatically detects the CTs number and
direction of CTs.
•
A value of 1 assumes a specific orientation and direction of CTs.
0
N/A
CTTurnsRatio
•
Turns ratio of the CTs installed.
•
Default turns ratio of 1500 is compatible with included clamp type CT's
•
If installation restriction requires larger accessory CT's, set point shall be
adjusted to 3000.
1500
Turns