Commissioning and Setup
Installation Manual for Generac PWRCell Inverter
21
Section 6: Commissioning and Setup
System Configuration
The Generac PWRcell system is a flexible, highly
customizable system that can be configured in a number
of ways to meet customer need. Correct system
configuration requires selecting the right equipment and
the correct operational mode for the system. See the
Generac PWRcell Inverter Owner’s Manual for
information on operational modes and other user-
configurable settings.
Enabling Islanding
Systems with the Generac PWRcell Battery must have
the EnaIslanding setpoint set to ON to island. This set-
point is accessible through the Mod. Settings menu via
the inverter device page. See the Generac PWRcell
Inverter Owner’s Manual for information on accessing
and adjusting the EnaIslanding setpoint.
General Information
All REbus devices are configured and controlled through
the Generac PWRcell Inverter. Connected devices will
appear on the LCD display.
Commissioning the System
NOTE:
See the Generac PWRcell Commissioning Quick
Start Guide for more information.
Commissioning consists of five steps:
1.
2.
3.
Configuring Custom Grid Settings (optional)
4.
5.
Before powering up the system for the first time:
•
Verify AC voltage is within the specified range for
system configuration.
– 240 V split-phase
– 208 V 3-phase
•
Verify all wiring terminations are tight and secure.
•
Verify DC wiring field terminations are secure and
polarity is correct.
•
Verify DC breakers for all connected devices are
turned ON.
Inverter Power-up
Turn ON the main AC breaker to power-up the inverter.
See
. On power-up, the home screen will
appear on the control panel LCD with the operational
mode listed at the top of the home screen.
010006
Figure 6-1. Inverter Power-Up
NOTE:
If there is no grid power at the site and the sys-
tem includes Generac PWRcell Battery, blackstart can be
used to start the system from the battery. See the Gen-
erac PWRcell Owner’s manual for information on black-
starting a system.
Selecting an Operational Mode
NOTE:
See the Generac PWRcell Inverter Owner’s
Manual for more information on operational mode
options.
To select an operational mode:
1.
See
. While viewing the home screen
press the center button.
009965
Figure 6-2. Selecting Operational Modes (1 of 4)