Commissioning and Setup
22
Installation Manual for Generac PWRCell Inverter
2.
See
. A list of operational modes will be
displayed with the current mode marked with an
asterisk.
NOTE:
The list of modes may not include all those
009966
Figure 6-3. Selecting Operational Modes (2 of 4)
3.
See
. Use the up and down arrows to
highlight the desired mode and press the center
button to select.
009967
Figure 6-4. Selecting Operational Modes (3 of 4)
4.
Arrow right and press the center button to select
Confirm.
5.
. Verify the mode listed at the top of
the home screen is the desired mode.
009968
Figure 6-5. Selecting Operational Modes (4 of 4)
Configuring Custom Grid Settings (optional)
By default, all Generac PWRcell Inverters ship in compli-
ance with UL1741, including IEEE1547. If the system
needs to be configured to comply with a different grid
interconnection standard, activate the new configuration
before proceeding.
Enabling REbus Devices
(000627)
DANGER
Electrocution. Never enable any device during an
installation or while wires are exposed. Doing so
could result in death, serious injury, equipment or
property damage.
NOTE:
All Generac PWRcell devices are enabled and
configured individually through the Generac PWRcell
Inverter control panel.
Following installation, the inverter must be enabled
before all other REbus devices.
To enable the inverter:
1.
See
. Use the right arrow key to scroll
the inverter device page.
2.
Verify inverter status reads disabled.
010010
Figure 6-6. Enabling Inverter (1 of 4)
3.
Press the center button.
4.
See
. Highlight Enable and press the
center button.
009656 010011
Figure 6-7. Enabling Inverter (2 of 4)