Location and Compliance
10
Installation Manual for Generac PWRcell Inverter
Voltage and Frequency Trip Thresholds
This unit or system is provided with fixed trip limits and
shall not be aggregated above 30 kW on a single point of
common connection.
All PWRcell inverters are shipped from the factory in
compliance with all UL1741 requirements, including
IEEE1547. If permission to operate (PTO) is dependent
on compliance to a specific utility standard, follow the
steps covered in
section in
this manual.
Voltage Trip Thresholds
See
for the default fixed voltage trip setpoints.
All over voltage and under voltage trip conditions result in
a 300-second restart delay time after the trip threshold
has been exceeded for the listed number of cycles.
Frequency Trip Thresholds
See
for the default fixed frequency trip set
-
points. All over frequency and under frequency trip condi
-
tions result in a 300-second restart delay time after the
trip threshold has been exceeded for the listed number of
cycles.
*Value of 999 indicates a disabled threshold for voltage trips
**Value of zero indicates a disabled threshold for frequency trips
Table 3-2. Voltage Trip and Frequency Thresholds
Voltage Trip Thresholds
Frequency Trip Thresholds
Threshold
Threshold
(% of nominal)
No. of Cycles
Threshold
Hz Over/
Under Nominal
No. of Cycles
OV1
110
120
OF1
0.5
120
OV2
120
10
OF2
2
6
OV3
130
1
OF3
1.3
0
OV4
999*
1
OF4
0**
1
UV1
88
120
UF1
0.5
120
UV2
50
10
UF2
2
10
UV3
999*
1
UF3
0**
1
UV4
999*
1
UF4
0**
1