Owner’s Manual for Generac PWRcell Inverter
11
General Information
Sell
Sell mode commands the system to export all available
power to the grid. Any connected batteries drain to the
grid until their state of charge reaches the MinSoCRsrv
setpoint. Once a battery is depleted to this point, it will not
charge again until either of the following are true:
•
The solar energy available exceeds the inverter
max AC Power.
•
The inverter system mode is changed to a system
mode prioritizing battery backup.
See the Generac PWRcell Battery Installation Manual for
more information.
Export Override
NOTE:
This feature requires CTs to be properly installed
and calibrated prior to use. For more information on CT
calibration, see the PWRcell Inverter Installation Manual.
NOTE:
This feature is NOT intended to serve as a
means of achieving compliance to Utility interconnection
requirements. For information on export limiting settings
related to Utility compliance, see the PWRcell Inverter
Installation Manual.
When enabled, Export Override allows the user to restrict
inverter export such that excess power is not sent back to
the grid. The system limits solar power generation to
match power consumption measured by the PWRcell
CTs. This feature is suitable as a simple and easy option
for systems pending permission to operate (PTO) where
the Utility does not specify a requirement for the system
to be de-energized or otherwise disabled pending
approval. Using the Inverter control panel, a user can find
this feature on the Mod. Settings sub-menu within the
Inverter device page.