Owner’s Manual for Generac PWRcell Inverter
5
General Information
Section 2: General Information
Specifications
Description
Units
XVT076A03
XVT114G03
Max. cont. grid-tied AC power @ 122°F (50°C)
kW
7.6
11.4
Max. cont. islanded AC power @ 104°F (40°C)
with single 6 module battery cabinet
1
kW
9.0
9.0
Max. cont. islanded AC power @ 104°F (40°C)
with 2 battery cabinets (8 modules minimum)
kW
11.0
Range 9.6 to 11.0*
Max. cont. Islanded AC power @ 122°F (50°C)
kW
8.8
Range 7.5 to 8.8*
Peak motor starting current (2 sec)
A rms
50
Normal output frequency AC
Hz
60
Grid Voltage Line to Neutral (L-N)
VAC
120
Grid Voltage Line to Line (L-L)
VAC
240
208
Peak efficiency
%
96
97
CEC weighted efficiency
%
96.5
96.5
AC terminals wire size
AWG
14 to 6
DC terminals wire size
AWG
18 to 6
STOP terminals wire size
AWG
28 to 16
Weight
lb (kg)
62.7 (28.4)
Thermal management
-
forced convection
Weatherization rating
-
NEMA Type 3R
Enclosure Material
-
powder-coated steel
Description
Units
Min
Nominal
Max
REbus voltage
V dc
360
380
420
REbus current
A dc
30
2
REbus Input short circuit current
3
A dc
30
REbus Input source backfeed current to input source
A dc
30
Output power factor rating AC
-
1
Operating voltage range AC, XVT076A03 (L-N)
V rms
108
120
130
Operating voltage range AC, XVT076A03 (L-L)
V rms
216
240
260
Operating voltage range AC, XVT114G03 (L-N)
V rms
108
120
130
Operating output voltage range AC, XVT114G03 (L-L)
V rms
184
208
228
Continuous output current AC grid-tied
A rms
32
PCS controlled current grid-tied
Arms
32
Continuous output current AC islanded
A rms
42
Output fault current duration
A / ms
50 / 200
Full Power operating ambient temperature range
4
°F (°C)
-4 (-20)
+122 (+50)
Utility interconnection voltage and frequency trip limits and
trip times
See Voltage and Frequency Trip Thresholds in PWRcell Inverter
Installation Manual for more information.
Trip voltage and frequency limits
Trip voltage accuracy
Trip time accuracy
%
2% +/- 2 cycles
1
Peak Performance
2
Inverter limits its REbus current to adhere to its AC power rating.
Total REbus current capability from multiple REbus sources
may safely exceed this value as the inverter safely limits the amount utilized.
3
Rating for one DC input. Four total.
4
Includes ambient temperature rising from inverter operation.
* In Island mode XVT114G03 Protected loads only supply 2 phases 120 VAC L-N, 208 L-L which results in lower power than in grid
tied 3 phase mode.The low value of the range is for full L-L loading while high value of the range is full L-N loading.