SPECIFICATIONS
GENERATOR
Type ............................................................................. Synchronous
Rotor Insulation ............................................................Class F or H
Stator Insulation .................................................................. Class H
Total Harmonic Distortion ......................................................< 3.5%
Telephone Interference Factor (TIF) ..........................................< 50
Alternator Output Leads 3-phase ........................................... 4-wire
Bearings .........................................................................Sealed Ball
Coupling .......................................................................Flexible Disc
Load Capacity (Standby Rating) ............................................30kW*
*
NOTE: Generator rating and performance in accordance with ISO8528-5, BS5514, SAE J1349,
ISO3046 and DIN 6271 Standards. KW rating is based on LPG fuel and may derate with natural
gas.
Excitation System ....................................................................Direct
Generator Output Voltage/kW - 60 Hz
kW
Amp CB Size
120/240V, 1-phase, 1.0 pf
30
125
150
120/208V, 3-phase, 0.8 pf
30
104
125
277/480V, 3-phase, 0.8 pf
30
45
50
Generator Locked Rotor KVA Available @ Voltage Dip of 35%
Single-phase or 208 3-phase ............................................. 60 KVA
480V, 3-phase .................................................................... 70 KVA
ENGINE
Make ................................................................................... Generac
Model ...................................................................................... V-type
Cylinders and Arrangement ............................................................ 6
Displacement ....................................................................... 3.0 Liter
Bore ...................................................................................... 3.55 in.
Stroke ..................................................................................... 3.1 in.
Compression Ratio ...............................................................9.3-to-1
Air Intake System ...............................................Naturally Aspirated
Valve Seats ....................................................................... Hardened
Lifter Type .......................................................................... Hydraulic
Engine Parameters
Rated Synchronous RPM ..............................................60 Hz, 1800
HP at rated kW ..................................................................60 Hz, 48
Exhaust System
Exhaust Flow at Rated Output 60 Hz .................................. 200 cfm
Exhaust Temperature at Rated Output .................................. 890° F
Combustion Air Requirements (Natural Gas)
Flow at rated power, 60 Hz ................................................... 92 cfm
Governor
Type .................................................................................. Electronic
Frequency Regulation ...................................................Isochronous
Steady State Regulation ........................................................± 1/2%
Adjustments:
Speed ............................................................................ Selectable
Engine Lubrication System
Type of Oil Pump ...................................................................... Gear
Oil Filter .............................................................Full Flow, Cartridge
Crankcase Oil Capacity ....................................................4 U.S. qts.
COOLING SYSTEM
Type ....................................................................................... Closed
Water Pump .................................................................... Belt Driven
Fan Speed ................................................................................ 2150
Fan Diameter .....................................................................18 inches
Fan Mode ..............................................................................Pusher
Air Flow (inlet air including alternator and
combustion air) .......................................................... 2460 ft3/min.
Coolant Capacity ........................................................ (2.5 U.S. gal.)
Heat Rejection to Coolant ..........................................115,000 Btu/h
Maximum Operating Air Temp. on Radiator ..............60° C (150° F)
Maximum Ambient Temperature ................................50° C (140° F)
FUEL SYSTEM
Type of Fuel ......................................... Natural Gas, Propane Vapor
Carburetor ...................................................................... Down Draft
Secondary Fuel Regulator .................................................Standard
Fuel Shut-off Solenoid ........................................................Standard
Operating Fuel Pressure ...................... 5 in. - 14 in. Water Column
Fuel Consumption - ft
3
/hr (Natural Gas/LPV)
Exercise
25%
50%
75%
100%
Cycle
Load
Load
Load Load
70/28.3 111/45 214/86.1 298/120 412/166
ELECTRICAL SYSTEM
Battery Charge Alternator ............................................12V, 30 Amp
Static Battery Charger ............................................................2 Amp
Recommended Battery ................................................ 24F 525CCA
System Voltage .....................................................................12 Volts
Voltage Regulator
Type .................................................................................. Electronic
Sensing ........................................................................ Single-phase
Regulation ................................................................................± 1%
Features ................................................. V/F Adjustable, Adjustable
Voltage and Gain LED Indicators
Power Adjustment for Ambient Conditions
Temperature Deration
3% for every 10° C above °C ..................................................... 25
1.65% for every 10° above °F .................................................... 77
Altitude Deration
1% for every 100 m above m ................................................... 183
3% for every 1000 ft. above ft. ................................................. 600
Controller .................................................R-100
6-1
Standby Generator Sets
Specifications
GenSpec002 Rev.
C 11/05
Summary of Contents for Quietsource 005220-0
Page 25: ...Standby Generator Sets Notes ...
Page 26: ......
Page 28: ......
Page 30: ......
Page 32: ......
Page 34: ......
Page 36: ......
Page 38: ......
Page 40: ......
Page 42: ......
Page 43: ......
Page 44: ......
Page 46: ......
Page 48: ......
Page 50: ......
Page 51: ......
Page 52: ......
Page 53: ......
Page 54: ......
Page 55: ......
Page 56: ......
Page 57: ......
Page 58: ......
Page 59: ......