Models FL3100/3101
47
Field of View
*
: (Figure 3-A)
FL3100 120° maximum conical
FL3101 140° maximum conical
NOTE
*
- Response Times and Field of View data have been derived by testing
the Models FL3100/FL3101 Flame Detectors with a 1 square foot gasoline fire.
One cup of unleaded gasoline on top of a one-inch layer of water was ignited for
each test. These are typical values and different results may occur depending on
the variation of each fire.
Sensitivity:
50 feet (15.2m); Maximum distance for a 1 square foot (.093m
2
) gasoline fire to
be reliably detected. (For settings see Section 4.4 User Selectable
Options/Factory Defaults).
If need to detect fires at distances over 50 feet, contact General Monitors directly
for more information.
Maximum Cable Parameters:
Output Signal
9000 feet (2750m), maximum 50 Ohms loop, with maximum 250 Ohms input
impedance of readout unit.
Remote power supply
3000 feet (930 m), maximum 20 Ohms loop and 24VDC minimum. (See Section
3.3 Terminal Connections)
Warranty:
Two Years
9.2.2 Mechanical Specifications
Enclosure Material:
Material:
Aluminum (AL) A-356, Stainless Steel (SS): Natural 316
Color:
Aluminum Red
Finish:
Aluminum: Chemical Film per MIL-C-5541, Epoxy
Powder Coated
Dimensions:
Height
6.0
in
(15.2cm)
Width
6.0 in
(15.2cm)
Depth
5.5 in
(14.0cm)
Weight
5 lbs
(2.3 kg) AL
16 lbs
(7.3 kg) SS
Cable Entry:
2 x 25mm ISO or 2 x PG 13.5 or 2 x 20mm ISO or 2 x ¾” NPT.
Each unit has an Exd approved stopping plug installed, plus Red Dust cap. Dust
caps must be replaced by Exd IIB Approved cable glands and must not be left
on the unit when powered up.