Models FL3100/3101
49
9.2.4 Environmental Specifications
Operating temperature range: -40°C to 85°C
-40°F to 184°F
Storage temperature range:
-40°C to 85°C
-40°F to 184°F
Humidity range:
0 to 100% RH
non-condensing
Modbus RTU Protocol
For detailed information on addressing, baud rate, data format, read commands,
write commands, register details, register locations, refer to the Appendix.
9.3 Approvals
CSA certified
ULC, CENELEC & CE Marking pending.
9.4
Accessories
9.4.1 Mounting Swivel/Union
A mounting swivel and union are available to connect ¾” conduit into the base of
the Model FL3100/FL3101. The swivel design allows for optical alignment
adjustments for the Models FL3100 and FL3101 when using rigid conduit.
NOTE - Swivel is only rated for Class I, Division 1 and 2, Group C & D areas.
For Group B areas, use mounting bracket. Swivel is not approved for CENELEC
requirements.
9.4.2 Mounting Bracket
A mounting bracket is available to mount the FL3100/FL3101 to a wall, pole, etc.
The mounting bracket design allows for optical alignment adjustments for the
Models FL3100 and FL3101 when installed to a fixed installation.
9.4.3 Optical Air Guard
An optical air guard is available for applications such as paint spray booths,
which require a method to keep detector optics clean. The air guard mounts at
the front of the FL3100/FL3101 and has a connection for shop air. The air, when
turned on, creates an air wall to keep optics clean.
9.5 Storage
The Flame Detectors should be stored in a clean, dry area and within the
temperature and humidity ranges quoted in Section 9.2.4, Environmental
Specifications.