Models FL3100H/3101H
11
Figure 9: FL3100H (UV/IR) Hydrogen Flame Detector Field of View
NOTE:
Response Times and Field of View data have been derived by testing the Model
FL3100H flame detector with a flame from a round 6 inch diameter burner. The
hydrogen gas was supplied from a high pressure tank via a reducing regulator, set to
12 psi. This produces a flame 6 inches in height. The FL3100H-Hydrogen detector can
be tested by the TL105 as far as 40 feet. These are typical values and different results
may occur depending on the variation of each fire.
NOTE:
The FL3100H-Hydrogen detector is not FM approved.
Summary of Contents for FL3101H
Page 2: ...Models FL3100H 3101H ii This page intentionally left blank ...
Page 22: ...Models FL3100H 3101H 15 Figure 14 P N 71072 Rear View Mounting Bracket Drawing ...
Page 70: ...63 Models FL3100H 3101H 10 7 Final Assembly Figure 24 P N 71450 FL3100H UV IR Final Assembly ...
Page 71: ...Models FL3100H 3101H 64 Figure 25 P N 71451 FL3101H UV Final Assembly ...