FL4000
44
Register
Address
(Hex)
Parameter
Function
Data
Type
Data Range Access
0x0012
Remote Alarm
Test
Activates Warn & Alarm
Relays
Numeric
Value
1 = Alarm
test, 0 =
done test.
R/W
0x0013
Clear COPM Fault
Counts
Reset COPM Counters to
zero.
Bit Map
Bit 1 =
Reset
W
0x0014
Sensor
Temperature
Temperature in
Degrees C
Numeric
Value
-128… +128 R
0x0015 –
0x001F
Reserved N/A
N/A
N/A N/A
0x0020
COM1 or COM2
Total Receive
Errors
Number of receive errors
on user MODBUS
Numeric
Value
0-65535 R
0x0021 Data
Errors
Number of illegal data
write errors on user
MODBUS
Numeric
value
0-65535 R
0x0022
Function Code
Errors
Number of function code
errors on user MODBUS
Numeric
Value
0-65535 R
0x0023
Starting address
errors
Number of starting
register address errors
Numeric
Value
0-65535 R
0x0024
Total COM1 Only
Receive Errors
Total communication
errors received on Comm
1
Numeric
value
0-65535 R
0x0025
CRC errors LO for
serial channel
Number of CRC LO
errors on user MODBUS
channels
Numeric
value
0-65535 R
0x0026
CRC errors HI for
user serial
channel
Number of CRC HI errors
on user MODBUS
channels
Numeric
value
0-65535 R
0x0027
Total Overrun
Errors COM1 Only
Total Overrun errors
received on comm
channel 1
Numeric
value
0-65535 R
0x0028 Reserved
N/A
N/A
N/A
N/A
0x0029
Total Framing
Errors COM1 &
COM2
Total Framing errors
received on comm
channels 1 & 2
Numeric
value
0-65535 R
0x002A-
0x002C
Reserved N/A
N/A
N/A N/A
0x002D
Clear Serial COM
Errors
Clear MODBUS
communication errors
Numeric
Value
1 W
0x002F COM2
Address
Set/view address on
MODBUS channel 2
Numeric
Value
1-247 R/W
0x0030
COM2
Baud Rate
Set/view baud rate on
MODBUS channel 2
Numeric
Value
Table 33
R/W
0x0031
COM2
Data Format
Set/view data format on
MODBUS channel 2
Numeric
Value
Table 34
R/W
0x0032 –
0x003E
Reserved N/A
N/A
N/A N/A