FL4000
55
This time is in seconds since January 1, 2000. This register should be read before register
0xAA.
4.10.49
Alarm Running Time in Seconds, Low Word (0x00AA)
This register reads the low word of the running time in seconds when the alarm event occurred.
This time is in seconds since January 1, 2000. This register should be read only after register
0xA9.
4.10.50
Alarm Clock Time: Year, Month (0x00AB)
These registers are described in Table 35 as item number 1.
4.10.51
Alarm Clock Time: Day, Hour (0x00AC)
These registers are described in Table 35 as item number 2.
4.10.52
Alarm Clock Time: Minute, Seconds (0x00AD)
These registers are described in Table 35 as item number 3.
4.10.53 Reserved
(0x00AE)
This register returns the value 0.
4.10.54 Reserved
(0x00AF)
This register returns the value 0.
4.10.55
Total Alarm Event Counter (0x00B0)
This reads the total number of alarm events have been stored in the unit.
4.10.56
Fault Running Time in Seconds, Hi Word (0x00B1)
This register reads the hi word of the running time in seconds when the fault event occurred.
This time is in seconds since January 1, 2000. This register should be read before register
0xB2.
4.10.57
Fault Running Time in Seconds, Low Word (0x00B2)
This register reads the low word of the running time in seconds when the fault event occurred. This
time is in seconds since January 1, 2000. This register should be read only after register 0xB1.
4.10.58
Fault Clock Time: Year, Month (0x00B3)
These registers are described in Table 35 as item number 1.
4.10.59
Fault Clock Time: Day, Hour (0x00B4)
These registers are described in Table 35 as item number 2.
4.10.60
Fault Clock Time: Minute, Seconds (0x00B5)
These registers are described in Table 35 as item number 3.