FL4000
62
8.0 Appendix
8.1 Warranty
General Monitors warrants the FL4000 to be free from defects in workmanship or material
under normal use and service within two (2) years from the date of shipment.
General Monitors will repair or replace without charge any equipment found to be defective
during the warranty period. Full determination of the nature of, and responsibility for, defective
or damaged equipment will be made by General Monitors’ personnel.
Defective or damaged equipment must be shipped prepaid to General Monitors or the
representative from which shipment was made. In all cases, this warranty is limited to the cost
of the equipment supplied by General Monitors. The customer will assume all liability for the
misuse of this equipment by its employees or other personnel.
All warranties are contingent upon proper use in the application for which the product was
intended and do not cover products which have been modified or repaired without General
Monitors’ approval or which have been subjected to neglect, accident, improper installation or
application, or on which the original identification marks have been removed or altered.
Except for the express warranty stated above, General Monitors disclaims all warranties with
regard to the products sold, including all implied warranties of merchantability and fitness and
the express warranties stated herein are in lieu of all obligations or liabilities on the part of
General Monitors for damages including, but not limited to, consequential damages arising out
of / or in connection with the use or performance of the product.
8.2 Specifications
8.2.1 System
Specifications
Typical Response Time:
≤
10 sec for heptane fires when detector is on axis to fire source;
≤
30 sec when detector is at angles of ±45º
Field of View
9
:
90
°
@ 210 ft (64 m), 100
°
@ 100 ft (31 m)
Sensitivity:
60 ft (18 m), 120 ft (37 m), and 210 ft (64 m) for low, medium, and
high sensitivities, respectively. Maximum distance for a 1 square
foot (0.093 m
2
) n-heptane
fire to be reliably detected. For settings
see 3.7 Switch Selectable Options.
NOTE
:
Response Times and Field of View data were obtained from tests with a 1 square foot
of heptane fire. These are typical values and different results may occur depending on
the variation of each fire.
9
Maximum specified FOV
is the angle at which FL4000 can detect the flame at 50% of the maximum specified
range.