FL4000
63
8.2.2 Mechanical
Specifications
Enclosure material:
316 Stainless Steel
Color: Metal
Finish: Polished
/eggshell
8.2.3 Dimensions
Height:
6.26" (159 mm)
Diameter:
3.50" (89 mm)
Weight:
6.9 lb. (3.1 kg)
8.2.4 Electrical
Specifications
Nominal supply
voltage: Range:
24 VDC
20 to 36 VDC
Maximum supply
current:
150 mA
Maximum output
signal load:
600
Ω
@ 24 VDC
Dual MODBUS HART
Output signal range:
0 to 20 mA
3.5 mA
FAULT signal:
0 to 0.2 mA
3.5 mA
COPM fault signal:
2.0 ± 0.2 mA
3.5 mA
Ready signal:
4.3 ± 0.2 mA
WARN signal:
16.0 ± 0.2 mA
ALARM signal:
20.0 ± 0.2 mA
Relay Contact
Ratings:
8 A @ 250 VAC,
8 A @ 30 VDC,
Resistive MAX
RS-485 Output:
Baud Rate:
RFI/EMI Protection:
Status Indicator:
MODBUS
128 units in series MAX
(247 units with repeaters)
2400, 4800, 9600, 19200, and 38400 Baud
(See Terminal Connections 3-4 for Alarm Output Connections)
Complies with EN6100-6-4: 2001 and EN50130-4: 1995+A1: 1998
Two LED’s indicate status, fault conditions
8.2.5 Environmental
Specifications
Operating temperature
range:
-40°F to 176°F (-40°C to 80°C)
Storage temperature range:
-40°F to 176°F (-40°C to 80°C)
Humidity range:
0 to 95% RH, non-condensing
8.2.6 Maximum
Cable
Parameters
0-20mA Output Signal
9,000 ft (2,750 m), maximum 50
Ω
loop, with maximum 250
Ω
input impedance of readout unit.
Remote Power Supply
3,000 ft (930 m), maximum 20
Ω
loop and 24 VDC minimum (Section 3.6 ).