General Monitors configures the IR400 with three calibration input options: magnetic switch
(default), manual solenoid, and automatic remote gas calibration device (ARGC). To use the
manual solenoid or ARGC, purchase a factory configured IR400 or change the calibration input
via Modbus or HART.
4.1.5 IR400 Analog Output (AO) Interpretation
Current Level (mA)
Meaning
0
Startup mode and critical fault for non HART unit
1.5
Zero, Calibration and Gas Check Mode
2 Non
critical
fault
4 – 20
0 – 100% LEL or % by Volume
20.1 – 21.7
Over range
Table 3: IR400 without HART Option
Current Level (mA)
Meaning
0
Startup mode and critical fault for non HART unit
1.25
Startup mode and critical fault if current range is low
1.5
Zero, Calibration and Gas Check Mode
2
Non critical fault
3.5
All faults and startup if unit is configured with current
range set to “high”
4 – 20
0 – 100% LEL or % by volume
20.1 – 21.7
Over range
Table 4: IR400 with HART Option