concentration. From the instant of exposure to this gas mixture the instrument shall respond to
provide an indication within the time specified as follows: 50% of full scale gas concentration in
10 sec, and 90% of maximum indicated gas concentration in 30 sec. The products offered by
GM are not for the purpose of testing T response time, but as a method to allow a user to check
that the unit is responding to gas and that final response is within tolerance.
The products offered by GM are not for the purpose of testing T response time, but as a
method to allow a user to check that the unit is responding to gas and/or that final response is
within tolerance. If it’s required to demonstrate a reading of 50% LEL at site this can be
achieved using the calibration cup, however it should be noted that you need to apply the test
gas for approximately three minutes to get a reading of 50% LEL. This time is due to the
ambient air located in the optical path of the detector having to be replaced progressively by the
test gas. This replacement of ambient air is quicker at the beginning but longer for the last
percentage because it is linked to the slow replacement of air dilution by the test gas. This test
is only to indicate a gas level of 50% LEL within the calibration cup and is not a reflection of the
response time of the detector.
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...