6.0 Troubleshooting
The IR400 will alert the operator that there are problems in a number of ways. The table on the
following page shows the value for the analog output, the value read through Modbus register 2
(if Modbus is being used), and the fault code, shown as F and a number, on the IR4000 display
(if connected).
If the IR400 is connected to a zero switch, then the LED in the zero switch will blink at a rate of
5 flashes per second to show that the detector needs attention.
HART Troubleshooting
1. Verify that the IR400 is configured for HART
2. Verify that the HART modem or HART handheld device (375 or 475) is working by
checking it against another HART field device
3. Verify that the HART software or handheld device has the DD for the IR400. If the DD is
not present, download it from the HART Communication Foundation (HCF) website.
4. Verify the IR400 wiring
5. Verify that power is off when removing or attaching wires
-
Red to power
- Black
to
common
-
White to a 250 ohm resistor, and the other end of resistor to common. Resistor
tolerance should be +/-5% or less.
-
Verify HART modem or 475 wiring: Leads are across the 250 ohm resistor
-
After verifying the IR400 wiring, verify that power is on to the IR400 and to the HART
modem or handheld device
6. Verify IR400 4-20mA output. When no gas and no faults are present, a voltmeter across
the 250 ohm resistor will read 1.0 volt DC.
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...