Model IR400
33
9.3 Specifications
9.3.1 System Specifications
Detector Type:
Infrared absorption
Detector Life:
Greater than 5 years
Measuring Range:
0 to 100% LEL
Zero Drift:
< 2% per year
Response Time:
(With 100% LEL methane applied)
(With 100% LEL ethylene applied)
T50
≤
7 seconds, T60
≤
8 seconds
T90
≤
10 seconds
T50
≤
5 seconds, T60
≤
6 seconds
T90
≤
11 seconds
Accuracy @ 25º C:
±3% FS
≤
50% FS, ±5% FS > 50% FS
Gas Calibrations
Methane, propane, ethane, ethylene, butane,
hexane, pentane at LEL levels defined by ISO
10156/NFPA 325 and at levels defined by IEC
61779-1.
Consult factory for other calibrations.
Readout/Relay Display
Modules:
DC110: Multi-Channel, Rack Mounted
1
DC130: Dual Channel, Rack Mounted
2
TA102A: Single Channel, Zero Two Series
3
IR4000 display and relay alarms
Malfunctions Monitored:
Re-calibration Error
Optics Failure/Blockage
Low Supply Voltage
Reference or Active Lamp Failure
Heater Failure
Time to Re-zero unit
Program Memory Checksum Error (EPROM)
Data Non-Volatile Memory Checksum Error
(EEPROM)
Short Circuit on CAL_IO Wire
Warranty:
Two years
Approvals:
CSA
FM
CE Marking
ATEX
IECEx
SIL 3 suitable
FM required statement: “This Approval does not include or imply Approval of apparatus to
which the subject instrumentation may be connected. In order to maintain an FM Approved
system, the apparatus to which this instrument is connected, must also be Approved by FM
Approvals.”
1
DC110 is not approved for use in ATEX installations
2
DC130 is not approved for use in ATEX installations
3
Rev E S/W and up for EU installations
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...