9.3.2 Mechanical Specifications
Length:
8.87 inches (225 mm)
Diameter:
2.9 in (74 mm)
Weight:
3 lbs (1.35 kg) for aluminum
6 lbs (2.7 kg) for stainless steel
Mounting:
3/4" NPT threads
Enclosure:
Marine Aluminum or Stainless Steel; Explosion
proof, IP66, Type 4X
9.3.3 Electrical Specifications
Input Power:
absolute min
20 V
nominal
24
V
absolute max
36 V
max. wattage
4.8 W @ +24 VDC
max. current
200 mA @ +24 VDC
ripple maximum allowed
1 V pk-pk
•
NOTE:
Customer supplied PSU must meet requirements IEC 1010-1 limiting current to
8A under Fault conditions, in order to comply with CE Marking requirements.
Analog Signal:
Range
0 - 21.7 mA
Load (max. resistance)
600
Ω
Current Level (mA)
Meaning
0
Startup mode and critical fault for non HART unit
1.25*
Startup mode and critical fault for HART unit
1.5*
Zero, Calibration and Gas Check Mode
2*
Dirty
Optics
4 – 20
0 – 100% LEL
20.1 – 21.7
Over range
* HART units can be configured to never output current less than 3.5 mA if the host equipment
is incapable of working below this level.
Area Classification:
Class I, Divisions 1 & 2, Groups B, C and D (Ta = -40°C to
+75°C), (Ta = -40°C to +60°C for ethylene only), IP66, Type
4X
Ex d, IIB+H
2
T5 Gb, IP66 (Ta = -60°C to +75°C)
Ex t IIIC T100°C Db
RFI/EMI Protection:
Complies with EN50270, EN61000-6-4
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...