Model IR400 HART
5
8.0 Universal Commands
Command 3 returns the current loop variable and the primary variable for a total of 9 bytes
returned. Command 9 returns the PV only.
9.0 Common Practice Commands
The following common practice commands are implemented.
Supported Commands
The following common-practice commands shown in Table are implemented:
Table 3: IR400 – Common Practice Commands
Command
Number
Byte
Number
Meaning
Command
38
N/A
Reset Configuration Changed Flag.
Command
48
0
Returns Priority Fault, High Byte
Command
48
1
Returns Priority Fault, Low Byte
Command
48
2
Returns error status (same as Modbus register x02), High Byte
Command
48
3
Returns error status (same as Modbus register x02), Low Byte
Command
48
4
Returns Power Cycled Flag
Command
48
5
Returns Event Happened Flag
Command
48
6
Value = 0: All OK; Bit 0: Maintenance Required; Bit 1: Critical Fault
Command
48
7
Returns 0