Model IR400 HART
7
Command #136: Set Alarm Level
This sets the Alarm level.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm level, % of FS
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm level, % of FS
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 – 2
N/A
Undefined
3
Error
Passed Parameter Too Large
4 N/A
Undefined
5
Error
Too Few Data Bytes Received
6 – 15
N/A
Undefined
16 Error
Access
Restricted
17 –
127
N/A Undefined
Command #137: Set Warn Level
This sets the Warn level.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Warn level, % of FS
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
Alarm Warn level, % of FS