Model IR400 HART
10
0 - 3
Unsigned-32
Event Running Time (in Seconds)
4– 6
Date
Event Date: Day, Month, Year – 1900
7 Unsigned-8 Event
Hour
8 Unsigned-8 Event
Minute
9 Unsigned-8 Event
Second
10-13
Unsigned-8
Reserved = 0
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
Command #146: Read Alarm Event Log
This reads the Alarm Event Log as specified by the event log number. Event 0 is the most recent event.
Event 1 is the one just before that and so forth.
Request Data Bytes
Byte
Format
Description
None N/A
N/A
Response Data Bytes
Byte
Format
Description
0 - 3
Unsigned-32
Event Running Time (in Seconds)
4– 6
Date
Event Date: Day, Month, Year – 1900
7 Unsigned-8 Event
Hour
8 Unsigned-8 Event
Minute
9 Unsigned-8 Event
Second
10-13
Unsigned-8
Reserved = 0
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
Command #147: Read Fault Event Log
This reads the Fault Event Log as specified by the event log number. Event 0 is the most recent event.
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...