Model IR400 HART
15
Command #155: Get Event Index
This reads event logged index.
Request Data Bytes
Byte
Format
Description
None N/A
N/A
Response Data Bytes
Byte
Format
Description
0
Unsigned - 8
Event index
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1-127
Undefined
Command #156: Read Calibration Event Log
This reads Calibration Event Log as specified by the event log number. Event 0 is the most recent
event. Event 1 is the one just before that and so forth.
Request Data Bytes
Byte
Format
Description
None N/A
N/A
Response Data Bytes
Byte
Format
Description
0-3
Unsigned-32
Event Running Time (in Seconds)
4-6
Date
Event Date: Day, Month, Year – 1900
7 Unsigned-8 Event
Hour
8 Unsigned-8 Event
Minute
9 Unsigned-8 Event
Second
10 - 11
Unsigned-16
Reserved = 0
12 - 13
Unsigned-16
1 - Zero, 2 - Calibration
Command-Specific Response Codes