Model IR400 HART
19
Gas Selection Codes
Code
to read
/ write
Gas Type
0 Methane
1 Propane
2 N
Butane
3 Hexane
4
% by
volume
Methane
5
Special
Order
6 Ethane
7 Pentane
Command #170: Set Current Range
This sets the current range to be either one of 2 possible selections.
Request Data Bytes
Byte
Format
Description
0
Unsigned-8
0 – Range 3.5mA - 20mA, 1 -- Range 1.25 - 20mA
Response Data Bytes
Byte
Format
Description
0
Unsigned-8
0 – Range 3.5mA - 20mA, 1 -- Range 1.25 - 20mA
Command-Specific Response Codes
Code
Class
Description
0
Success
No Command-Specific Errors
1 - 2
Undefined
3
Error
Passed Parameter Too Large
4
Undefined
5
Error
Too Few Data Bytes Received
6 - 127
Undefined