Model IR400 MODBUS
7
0023h
•
Starting
Register Address
errors
Number of Starting
Register Address
errors.
Numeric
Value
0-65535 decimal
R
0024h
Reserved
N/A
N/A
N/A
N/A
0025h
•
CRC
errors HI
Number of CRC HI
errors
Numeric
Value
0-65535 decimal
R
0026h
•
CRC
errors LO
Number of CRC LO
errors
Numeric
Value
0-65535 decimal
R
0027h
•
Overrun
errors
Number of Overrun
errors
Numeric
Value
0-65535 decimal
N/A
0028h
Reserved
N/A
N/A
N/A
N/A
0029h
•
Framing
errors
Number of framing
errors
Numeric
Value
0-65535 decimal
R
002Ah
Reserved
N/A
N/A
N/A
N/A
002Bh
Reserved
N/A
N/A
N/A
N/A
002Ch
Reserved
N/A
N/A
N/A
N/A
002Dh
•
Clear
Comm. errors
Clears
communication errors
Numeric
Value
See description
W
002E-008Ch
Reserved
N/A
N/A
N/A
N/A
008D
Gas ID #
Read unique Gas
Identification Number
Numeric
Value
See table for
register 0x0003
R
008E – 00AF
Reserved
N/A
N/A
N/A
N/A
00B0h
•
Reset
Events
Clears events of
resets event flag
Numeric
Value
0- Clear Events,
1 – Resets Event
Happened flag
W
00B1h
•
Run Time
hi
High word of Run
Time in Seconds
Numeric
Value
0-65535 decimal
R/W
00B2h
•
Run Time
low
Low word of Run
Time in Seconds
Numeric
Value
0-65535 decimal
R/W
00B3h
Real Time Clock
Year, Month
Read/Set year and
month of RTC
Numeric
Value
1 –99 year, 1–
12 month
R/W
00B4h
Real Time Clock
Day, Hour
Read/Set day and
hour of RTC
Numeric
Value
1 – 31 day,
0 – 23 hour
R/W
00B5h
Real Time Clock
Minute, Second
Read/Set minutes
and seconds of
RTC
Numeric
Value
0 – 59 minutes
0 – 59 seconds
R/W
00B6h
Power Cycled
Flag
Time Reset After
power Cycled
Numeric
Value
0 = Time not
Reset, 1 =
Time Reset
R
00B7h
Event Index
Index of Logged
Events
Numeric
Value
0 - 9
R/W
00B8h
Running Time
Hi
Running Time Hi
for Warning Event
log entries
Numeric
Value
0 - 65535
R
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...