1.4.26 Beam Block Percentage (0x0054)
This register returns a value from 0-100. When the optical path of the IR400 is clear, the
reading is 0% blocked. When the register reads near 100 the optical path is blocked and
must be cleaned immediately. At 100% the IR400 indicates a fault condition and is no
longer capable of detecting gas. This register can be used for predictive maintenance.
1.4.27 Gas ID (0x008D)
This register provides a way to read the unique Gas ID number for the currently selected
gas. The table below shows the numbers for the gasses available in the IR400. This list
will be extended as more gasses are made available and will be consistent across
General Monitors’ product range.
Gas ID number (decimal)
Gas Type
100 Methane
101
Propane
102 Ethane
103
Hexane
104 n-Butane
105
Pentane
106
% by volume Methane
108
Ethylene
109 Benzene
114
Methane IEC
115 Propane
IEC
116
Ethane IEC
117 Pentane
IEC
120
n-Butane IEC
121 Hexane
IEC
1.4.28 Reset Events (0x00B0)
Writing 0 to this register clears all event counters, writing 1 – resets event happened flag.
1.4.29 Running Time in seconds hi word (0x00B1)
This sets/reads hi word of device running time in seconds. This value must be
read/written prior to running time low byte (register 0x00B2).
Summary of Contents for IR400
Page 2: ......
Page 15: ...Model IR400 11 Figure 5b IR400 Mounting Dimensions with a European Box ...
Page 20: ...Model IR400 16 Figure 7 Wiring Diagram from IR400 to Control Equipment ...
Page 41: ...Model IR400 37 9 6 Engineering Documentation ...
Page 45: ...Model IR400 HART Field Device Specification for Point IR Gas Detector ...
Page 78: ...Model IR400 Infrared Point Detector for Hydrocarbon Gas Applications Modbus programming guide ...