Model TA102A
10
CAUTION -
Contact with PC Board components should be avoided in order to prevent
damage by static electricity.
To connect wires to the terminal block on the Model TA102A, loosen the desired screw,
insert the stripped end of the wire and tighten. (Alternate connector styles available –
contact the factory).
For the rear terminal designations refer to Figure 21 below:
Figure 21 – Rear Terminal Designations
3.3.1 A2 Alarm
The terminal designations for the
A2
alarm outputs are:
Figure 22 – Terminal Designations for A2 Alarm Outputs
The
A2
alarm outputs are DPDT relays, 1 open collector output (
A2-OC
) that follows the
logic of the relays and 1 open collector output (
LA2
) that follows the blinking pattern of
the front panel LED. The A2-C1 designation is common for A2-1 & A2-2. The A2-C2
designation is common for A2-3 & A2-4. The normally open (
NO
) and normally closed
(
NC
) contacts depend on a user selectable option (see Chapter 5). The table below
refers to the proper open and closed
A2
alarm relay contacts while the unit is on power:
LABEL
TERM
DESCRIPTION
A2-C1
2d
Relay Common (1 & 2)
A2-1
4d
Relay Contact
A2-2 6d
Relay
Contact
A2-3
8d
Relay Contact
A2-4 10d
Relay
Contact
A2-C2
12d
Relay Common (3 & 4)
A2-OC
14d
Open Collector (OC)
LA2
24z
OC Logic for A2 LED (mimic)