3.5
Power wiring
Check that the power supply voltage to be connected matches the value indicated on the rating plate inside the
electrical panel.
Insert the power and ground connection cables into the electrical panel compartment using the strain reliefs
supplied, and connect to the terminals. An external fused disconnect must be installed.
All wiring must be in accordance with local, state and national electric codes.
NOTE: to avoid unwanted interference, the power cables should be kept separate from any control wiring.
All wiring must be in accordance with local, state and national electric codes.
Fig. 3.n
Model Code
Power supply
(single phase)
Steam Output
(lbs/hr)
Steam Output
(kg/h)
POWER
(kW)
CURRENT
(A)
EXTERNAL POWER WIRES EXTERNAL FUSE (A)
DS15
110Vac 50/60Hz
5.5
2.5
1.86
16.88
AWG10
25
RS15
110Vac 50/60Hz
5.5
2.5
1.86
16.88
AWG10
25
DS20A 230Vac
50/60Hz
7 3.2
2.36 10.27
AWG12
20
RS20A 230Vac
50/60Hz
7 3.2
2.36 10.27
AWG12
20
DS35 230Vac
50/60Hz 12 5.4
4.05 17.61 AWG10
25
RS35 230Vac
50/60Hz 12 5.4
4.05 17.61 AWG10
25
NOTE: Tolerance allowed on main voltage = -15% to +10%
Connect power wires to the power terminal block located at the bottom left of the control module.
.
Fig. 3.o
Connect the wiring ground wire to the unit’s chassis ground, located just behind the power wiring terminal block.
Fig.3.p