Alarms
In the event of an alarm, the red alarm LED will flash, the alarm relay will close, and the alarm code will flash in the display. Multiple alarms will flash in sequence,
alternating with the main display. Pressing the sel button for 2 seconds will reset the alarms, although still active alarms will continue to display.
Display Description
Action
Notes
E0
Control board configuration not valid
Unit disabled
Turn off, check control board, reprogram
E1
High current alarm
Unit disabled
Turn off, check connections, check cylinder (no
limescale bridges between electrodes, no electrodes
short-circuited)
E2
Low production, low supply water
conductivity or excessive foam/limescale in
the cylinder
Unit disabled.
Press “reset/sel” key for 1 seconds to reset.
Check supply water conductivity (too low?), replace
the cylinder.
E3
Cylinder lifetime expired (1200 hours)
Press “reset/sel” key for 1 seconds to reset. The warning will be
displayed 50 hrs later until the hour counter is reset and the
cylinder replaced.
Change cylinder (not urgent)
E4
Fill alarm, unable or slow fill
(current does not increase within timeout)
Press “reset/sel” key for 1 seconds to reset, otherwise the warning
will be reset automatically every 10 minutes until the supply water
is available again.
Check water supply and fill valve; check drain valve
for leakage
E5 Drain
alarm, unable to drain
(current does not decrease within timeout)
Press “reset/sel” key for 1 seconds to reset
Check drain valve and drain connection
E6 Cylinder
exhausted
(critical performance detected)
The warning is automatically reset if Elite Steam can produce the
demand, otherwise turn off and then on.
Change cylinder (urgent)
E7
Foam detected
Press “reset/sel” key for 1 seconds to reset
If it continues, do some cleaning cycles (read chap.
“Starting with a new cylinder”)
E8
Cylinder lifetime expired (2000 hours)
Reset the hour counter (read chap. Resetting the hour counter”)
Change the cylinder.
E9
High controller temperature (above 176 °F /
80 °C)
The warning is automatically reset if the temperature decreases
below 176 °F / 80 °C.
Check the ambient temperature, replace the
controller.